Idiomas disponibles

Remarks
• StartStopStatus_XXX
1. If there is an operation error, the Present_Value property will be set to ACTIVE regardless of
whether the A/C is in operation or not.
• SetTempStatus-XXX / SetLowerTempStatus_XXX / RoomTemp_XXX
1. This object is for indoor units only, and reports the room temperature data measured by the
indoor units.
• WrStartStopCommand_XXX
1. The command executed is transmitted to the A/C regardless of the status of the A/C.
2. The Present_Value property will not be used if a property has never been set in the past.
• FanSpeedStatus_XXX
1. The Present_value property will be set to "1:Low" as the default value if the property has never
been set in the past.
• SetUpperTempStatus_XXX
1. This object is for indoor units only, and reports the set upper temperature data measured by the
indoor units.
• MalfunctionCode_XXX
1. This object's error code descriptions should be referred to the corresponding table at the
"Reference LG original Error Code".
• ModeCommand_XXX
1. The Present_Value property will be set to "1: Cool" as the default value if property has never
been set in the past.
2. The air conditioner will ignore the command to an object that does not have right to select
operation mode. Therefore, the controlled/monitored system must not use this object for the air
conditioner without the right to select operation mode.
• FanSpeed Command_XXX
1. The A/C will disregard the command which the object which can't select the operation mode.
Therefore, controlled/monitored system shouldn't use the object which can't select the operation
mode.
• SetUpperTempCommand_XXX / SetLowerTempCommand_XXX
1. This unit is for indoor units only, and the approximate set upper(or lower) temperature range is
18 ~ 30 °C.
2. 1 °C is detected.