Unscrew the screw "A" from the pressure tap "B".
-
Position the pressure gauge.
-
Switch on the appliance and check that the pressure is the one intended:
-
otherwise check on the cause.
At the end of the operation, reassemble the appliance and check on the
-
connection.
ATTENTION: If the pressure measurement is not within the thresholds
stated in table 5, instead of installing the appliance you should contact
your gas provider to report a fault with your mains supply.
Close the gas valve, disconnect the pressure measurement device, do up the
screw you had previously undone and close the front panel
TABLE 5 – Permissible thresholds for the gas feed pressure
Gas
Natural gas G20
Liquid gas G30/31
5. REGULATION FOR OPERATION WITH OTHER TYPES OF GAS
In order to perform this operation the injectors have to be changed and the reduced
capacities and position of the primary air regulated as indicated below.
5.1 Replacing the injector of the main burner
In order to change the injector remove, by pulling it, the control panel. Using a
spanner unscrew the injector and replace it according to tables 2 and 3.
5.2 Replacing the injector of the pilot flame (Fig. 4)
The pilot flame is only accessible after having removed the control panel. It
has a fixed injector and no regulation of the primary air is required. In order
to change the injector "D" unscrew the attachment nut "E" and replace the
injector, according to table 2 or 3.
5.3 Regulating the reduced capacity (Fig. 5)
Unscrew the screw "F" of the minimum and turn it until the reduced capacity
indicated in table 2 or 3 is obtained. Check that the quantity of gas is
sufficient for maintaining a stable and even minimum and for resisting the
change from maximum to minimum capacity.
Caution: before using the appliance the plate has to be cleaned with hot water.
The appliance has to be used by qualified staff, since it is an appliance intended solely for professional kitchens. It also
has to be used under supervision and only for grilling food.
6.1 Lighting the pilot flame (Fig. 6)
Press on the knob "G" and turn it to the left as far as the pilot flame lighting position.
Keep the knob pressed and at the same time press piezoelectric ingnition button "H". After having lit the pilot
nominal
20
28 - 30/37
6. OPERATING INSTRUCTIONS
13
Fig. 3
Supply pressure [mbar]
min
17
20/25
A
B
max
25
35/45
Fig. 4
Fig. 5
Fig. 6