The following materials are prohibited : aluminium, aluminized and galvanized steel.
The following materials are approved : black plate (min. thickness 2 mm), enamelled plate (min. thickness 0.6 mm) and
stainless steel (min. thickness 0.4 mm).
The connector fitting should be visible over its entire length and capable of being swep mechanically. Expansion should
not adversely affect the conduit intake or discharge junctions or its own mechanical stability or that of the main smoke
flue. Its design, and more especially its connection to the smoke flue, should be such as to prevent the accumulation of
soot, notably during sweeping.
Connections to both the stove and the flue should strictly comply with DTU 24.2.2 and the conduit manufacturer's
specifications and should include all the fittings recommended (end fittings, connecting pieces etc...).
If the connector is to be horizontal, there should be an ascending slope of 5 cm per metre.
1.4 - DRAUGHT REQUIREMENTS
Draught is measured on the connector duct about 50 cm after the stove outlet.
The draught required for efficient working with the door closed is as follow :
.
6 Pa on slow (0,6 mm WG)
.
12 Pa on normal (1,2 mm WG)
The installation of a damper is strongly recommended.
A damper ensures an efficient operation, even where draught requirements are considerable (high flue and casing). The
damper should be visible and readily accessible (Fig. 2) and installed in the same room as the stove.
The damper does not habe any effect on the stove when the door is open.
1.5 - VENTILATION OF AREA IN WHICH STOVE IS INSTALLED
To ensure the stove works properly, air is required in addition to the air required for the statutory ventilation rate. This
additional air is compulsory when the dwelling is equipped with a mechanical ventilation system.
The air intake should be positioned either directly to the outside or in an area having ventilation to the outside. The intake
should be equipped with a protective grill.
The air outlet should be as near as possible to the stove. The user should be able to close it off when it comes
out directly into the room. While the appliance is being used, make sure that it is free of any obstructions.
The section of the air inlet must be at least equal to one quarter of the section of the chimney flue with a minimum of 50
cm² for a power rating less than or equal to 8 kW, and 70 cm² for a power rating between 8 KW and 16 KW.
It may be necessary to stop the mechanical ventilation fan so as to prevent smoke coming back into the room when the
door is opened.
1.6 – WALLS IN THE VICINITY OF THE APPLIANCE
The stove should be located at least 300 mm from the rear and side walls of the room and from any combustible
materials.
In order to protect the floor from heat radiation and possible falling combustible, install the unit on reflective metal
shielding (or on a tiled floor) which covers the entire surface underneath and in front of the unit.
The appliance must be set up on a floor with a sufficient bearing capacity. If the existing construction does not comply
with this prior requirement, appropriate measures must be taken to allow the floor to bear the appliance, such as setting
up a load distribution plate.
8