ELECTRICAL WORK
Electric safety regulations for the initial Installation
1.
In case of an unsafe (electrical, mechanical and/or refrigerant etc) situation do not install the aircon-
ditioner.
2.
Power voltage supplied should be in the range of 95%~105% of rated voltage on rating table.
3.
A creepage protector and a main power switch with a 1.5 times capacity of max. current of the unit
should be installed in power circuit.
4.
Ensure the air conditioner is grounded well.
5.
Connect the wires according the attached electrical connection diagram located on the panel of the
outdoor unit.
6.
All wiring must comply with local and national electrical standards and codes and be installed by qua-
lified and skilled people.
7.
An individual branch circuit and single receptacle used only for this air conditioner must be available.
See the following table for suggested fuse specifications:
Model
<
2.6 kW
2.6 kW < model ≤ 5.2 kW
NOTE!
The supply voltage should be consistent with the rated voltage
of the air conditioner.
Connect the cable to the outdoor unit
1.
The connection cables of indoor and outdoor units have been connected to the terminals on the con-
trol board except the grounding wire(Y/G), only white plug connectors exposed.
2.
Remove the control cover from the outdoor unit by loosening the screw.
3.
Hold the indoor plug connector and insert the mating plug connector located on the outdoor unit until
it fixed with a clicking sound. Secure the cable onto the control board with the cord clamp.
4.
Connect the grounding wire to the terminal on the control board individually.
5.
The electrical connection is finished now.
Outdoor unit
Control cover
Screw
Power supply
220-240V~50Hz
Outdoor unit
Plug connector
or
To indoor unit
Input Rated Current
(Switch/Fuse)
16A
20A
Secure the cable with cord clamp
4