6. Electrical work
L1 L2 GR
M1
M2
S
M1
M2
S
TB1
TB3
TB7
A
B
24 knock-out hole
(For transmission wires)
A Power source
C Screw on the electrical component box
B Transmission line
D Screw on the electrical component box
Fig. 6-1
6.3. Wiring transmission cables
1 Types of control cables
1. Wiring transmission cables
Types of transmission cables: Shielding wire CVVS or CPEVS or MVVS
Cable diameter: More than 1.25 mm
Maximum wiring length: Within 200 m
2. M- ET Remote control cables
ind of remote control cable
Shielding wire (2-core) CVVS, CPEVS or MVVS.
Cable diameter
0.5 to 1.25 mm
When 10 m [32 ft] is exceeded, use cable with
Remarks
the same speci cations as transmission line
wiring.
* Connected with simple remote controller.
sary.)
■
■ MA Remote Controller (Fig. 6-3)
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.
b.
se feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2
and terminal S on the transmission cable block of the indoor unit (IC).
c. Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the
terminal block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).
e. The jumper connector C 41 on the control panel does not change.
f.
Connect the terminal S on the terminal block for central control for the power supply unit to the ground terminal (
g. Set the address setting switch as follows.
nit
Range
IC (Main)
01 to 50
IC (Sub)
01 to 50
Outdoor nit
51 to 100
M- ET R/C (Main)
101 to 150
M- ET R/C (Sub)
151 to 200
MA R/C
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
<Permissible Lengths>
1 M-NET Remote controller
Max length via outdoor units: L
+L
1
Max transmission cable length: L
1
Remote controller cable length:
,
1
If the length exceeds 10 m [33 ft], use a 1.25 mm
calculation of the maximum length and overall length.
2 MA Remote controller
Max length via outdoor unit (M- ET cable): L
Max transmission cable length (M- ET cable): L
Remote controller cable length: m
1
C
D
CO D IT PLATE:
accessory
37 knock-out hole
(For power supply wires)
CO D IT WASHER:
accessory
2
2
[AWG 20 to AWG 16]*
se the most recent address within the same group of indoor units
se an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in
sequence with the IC (Main)
se the most recent address of all the indoor units plus 50
* The address automatically becomes "100" if it is set as "01 - 50".
Set at an IC (Main) address within the same group plus 100
Set at an IC (Main) address within the same group plus 150
nnecessary address setting ( ecessary main/sub setting)
+L
+L
and L
+L
+L
+L
and L
+L
+L
2
3
4
1
2
3
5
1
2
and L
+L
and L
+L
and L
+L
and L
3
4
3
5
2
6
7
,
+
,
10 m [33 ft] (0.5 to 1.25 mm
2
2
3
4
+L
+L
+L
and L
+L
+L
+L
1
2
3
4
1
2
6
and L
+L
and L
+L
and L
1
3
4
2
6
and m
+m
+m
and m
+m
+m
+m
1
2
3
1
2
3
4
(Fig. 6-1)
1. Connect the branch box transmission line to transmission terminal block (TB3),
or connect the wiring between outdoor units or the wiring with the centralized
control system to the centralized control terminal block (TB7).
When using shielded wiring, connect shield ground of the branch box transmis-
sion line to the screw (C or D) and connect shield ground of the line between
outdoor units and the central control system transmission line to the shield (S)
terminal of the centralized control terminal block (TB7) shield (S) terminal. In
addition, in the case of outdoor units whose power supply connector C 41 has
been replaced by C 40, the shield terminal (S) of terminal block (TB7) of the
centralized control system should also be connected to the screw (C or D) using
attached lead wire.
2. Conduit mounting plates are being provided. Pass the power supply and
transmission wires through the appropriate knock-out holes, then remove the
knock-out piece from the bottom of the terminal box and connect the wires.
3. Fix power source wiring to terminal box by using buffer bushing for tensile force
(PG connection or the like).
Caution:
system transmission line to this terminal bed (TB1B). If the transmission
3. MA Remote control cables
ind of remote control cable
Cable diameter
Remarks
* Connected with simple remote controller.
2
Controller name, symbol and allowable number of controllers.
ame
Outdoor unit controller
Indoor unit controller
Remote controller
Setting Method
+L
500 m [1640 ft] (1.25 mm
[AWG16] or more)
2
6
7
200 m [656 ft] (1.25 mm
2
[AWG16] or more)
[AWG20 to AWG16])
2
[AWG16] shielded wire. The length of this section (L
2
500 m [1640 ft] (1.25 mm
[AWG16] or more)
2
7
200 m [656 ft] (1.25 mm
2
[AWG16] or more)
7
200 m [656 ft] (0.3 to 1.25 mm
[AWG20 to AWG16])
2
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
(0.75 to 1.25 mm
2
Within 200 m
Symbol
Allowable number of controllers
OC
P MY-P36
M 1 1 to 7 units per 1 OC
IC
P MY-P48
M 1 1 to 10 units per 1 OC
RC
MA
Maximum of 2 per group
) in the electrical component box.
) should be included in the
8
)*
2
-
11