Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This sequencer is a direct replacement unit for sequenc-
ing both fan and heat. It can be used in a broad range of
gas and electric heating equipment and many other
applications where time delay is required.
This sequencer has a solid-state 24 volt heater, used to
energize the control, and a variety of normally open
contact sets. These contacts close and open within speci-
fied timings and are used to control the furnace fan and
heating elements on demand from a room thermostat.
THIS CONTROL MUST BE INSTALLED BY A QUALI-
FIED INSTALLER.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to re-calibrate this control will void the White-
Rodgers warranty.
WARNING
!
Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.
If in doubt about whether your wiring is millivolt,
low or line voltage, have it inspected by a quali-
fied heating and air conditioning contractor or a
licensed electrician.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD ST. LOUIS, MO 63123-5398
(314) 577-1300 FAX (314) 577-1517
24A34 SERIES
Fan/Heat Sequencer
INSTALLATION INSTRUCTIONS
This sequencer meets a wide variety of timing require-
ments and assures long life at high electrical loads as well
as minimum radio and TV interference.
Each sequencer is stamped with timing specifications.
For example, H1-20 C40-110 means the ON time for
heating is 1 to 20 seconds and the OFF time for cooling is
40 to 110 seconds. First contacts turn ON first and turn
OFF last; others are random On and random OFF.
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper
and dangerous operation.
Following installation or replacement, follow
appliance manufacturers' recommended instal-
lation/service instructions to insure proper op-
eration.
Printed in U.S.A.
except 24A34-15
DESCRIPTION
PRECAUTIONS
CAUTION
!
PART NO. 37-4799D
Replaces 37-4799C
9713

Publicidad

loading

Resumen de contenidos para Emerson White-Rodgers 24A34 Serie

  • Página 1 WHITE-RODGERS DIVISION Printed in U.S.A. PART NO. 37-4799D EMERSON ELECTRIC CO. Replaces 37-4799C 9797 REAVIS ROAD ST. LOUIS, MO 63123-5398 9713 (314) 577-1300 FAX (314) 577-1517...
  • Página 2 SPECIFICATIONS U.L. Ambient Rating: AC Electrical Ratings: -40° to +165°F (-40° to +74°C) Ambient self- Main Switch - (Terminals “M” or “F”) compensating Maximum Load: 30A at 240 VAC Terminals: Combined Load: 23A non-inductive plus 7A Main Contacts: Single or double 1/4" male quick- inductive at 240 VAC connect for combination loads Bimetal Heater - Input: 30 VAC 60 Hz.
  • Página 3 électricien qualifié. WHITE-RODGERS DIVISION Imprimé aux États-Unis No. DE PIÈCE 37-4799D EMERSON ELECTRIC CO. Remplace 37-4799C 9797 REAVIS ROAD, ST. LOUIS, MO 63123-5398 9713 (314) 577-1300 TÉLÉCOPIEUR : (314) 577-1517...
  • Página 4 SPÉCIFICATIONS Conditions ambiantes selon U.L. : Capacité électrique en courant alternatif : -40 à + 74°C (-40 à +165°F) à compensation Interrupteur principal – (Bornes “M” ou “F”) Charge maximale : 30 A à 240 V CA automatique Charge combinée : 23 A non-inductive plus Bornes : 7 A inductive à...
  • Página 5: Precaucion Caution

    WHITE-RODGERS DIVISION Impreso en EE.UU. No. DE PARTE 37-4799D EMERSON ELECTRIC CO. Reemplaza a 37-4799C 9797 REAVIS ROAD ST. LOUIS, MO 63123-5398 9713 (314) 577-1300 FAX (314) 577-1517...
  • Página 6: Especificaciones

    ESPECIFICACIONES Clasificación del Ambiente de U.L.: Capacidades eléctricas de CA: -40° a + 74°C (-40° a + 165°F) ambiente Interruptor principal – (Terminales “M” o “F”) autocompensador Carga máxima: 30A a 240 VCA Carga combinada: 23A no inductiva más 7A Terminales: inductiva a 240 VCA Contactos principales: Conexión rápida de 1/4 "...