Shutting Down The Unit; Process Of Shutting Down The Unit - Ingeteam INGECON SUN 1Play HF U Manual De Instalacion Y Uso

Ocultar thumbs Ver también para INGECON SUN 1Play HF U:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Shutting down the unit

15. Shutting down the unit
This section describes the procedure to shut down the unit. If you wish to work inside the unit, you must carry out
these instructions in the order shown here to remove the power.

15.1. Process of shutting down the unit

1.
Proceed to stop mode from the inverter display.
2.
Remove voltage from a means of disconnection outside the unit.
3.
Wait 5 minutes for the internal capacitances to discharge, the hot parts which may cause burns to cool
and the fan blades to stop turning.
4.
Check that there is no voltage at the DC and AC inputs.
5.
Signal cut-off point (Vac and Vdc) with a sign reading ¨Caution no switching...¨. If necessary, rope off the
work area.
ABF2013IQM01_ - Installation and Operation Manual
Ingeteam
EN
ES
39

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Tabla de contenido