WEG GRT7-TH4-R2 Manual De Instalación, Operación Y Mantenimiento página 21

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

¹ Item not supplied by GRAMEYER, please verify ratio specification (PAR/1 or PAR/5);
² if there is no Potentiometer connected, keep terminals short circuited;
³ 10A/250Vac switch to turn ON /OFF the regulator (Item not supplied by GRAMEYER)
* Output line voltage from generator in accordance to sensing class and the voltage level of the regulator power supply (Table
4.1).
ATTENTION
1. Before connecting the regulator to the generator, verify in the installation manual, the reference nominal
voltage.
2. When using an auxiliary coil, the connector E3/4, reference of the regulator circuit, should be the mandatory
common point between the coil and the generator
3. If the reference voltage is not equal to the output voltage of the generator, do not make the connections
without consulting the service department.
Generator
Exciter
Auxiliary
field
coil
F-
F+
Analog Input
Parallelism CT ratio In/x¹
¹
P1
S1
ON/OFF
key³
E
E
3
E3/4
S1
1
2
GRT7-TH4 R2
F+
F-
A- A+
DW CM
UP
Digital Input
Generator Voltage
from 170 to 280 Vca
from 320 to 600 Vca
from 520 to 640 Vca (*)
Automatic Voltage Regulator – GRT7-TH4-R2
P2
S2
S2
Potentiometer for
JHz
external voltage
regulation¹ ² ( 5k/3W)
www.weg.net
N
R
S
T
| 21