Slim Duct Type
Procedure
Using temp. setup
CODE No. [
Procedure
Using timer time
SET DATA [
Procedure
Push
flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
• To change other settings of the selected indoor
unit, repeat from Procedure
Use
To make settings after
repeat from Procedure
Procedure
When settings have been completed, push
button to determine the settings.
When
and then the display content disappears and the
air conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote controller is accepted.)
Setup of external static
pressure
Be sure to set up a tap change based upon the
resistance (external static pressure) of the duct to
be connected.
To set up a tap change, follow to the basic
operation procedure (
• Specify [5d] to the item code in procedure
• For the setup data of procedure
setup data of the external static pressure to be
set up from the following table.
<Change on wired remote controller>
Setup data
0000
0001
0003
0006
23-EN
3
/
buttons, specify
].
4
/
buttons, select
].
5
button. When the display changes from
2
.
3
.
button to clear the settings.
button was pushed,
2
.
6
button is pushed, "SETTING" flashes
1
2
3
External static pressure
10 Pa
Standard (At shipment)
20 Pa
High static pressure 1
35 Pa
High static pressure 2
50 Pa
High static pressure 3
When wireless remote controller is used
Change the external static pressure setting with
the DIP switch on the receiver section P.C. board.
For details, refer to the manual of the wireless
remote controller kit. The settings can also be
changed with the switch on the indoor
microcomputer P.C. board.
* However, once the setting is changed, setting to
0001 or 0006 is possible but setting to 0000
requires a setting data change to 0000 using the
wired remote controller (separately sold) with
the normal switch setting (factory setting).
Setup data
(Factory shipping)
To restore the factory settings
To return the DIP switch settings to the factory
settings, set SW501-1 and SW501-2 to OFF,
connect a separately sold wired remote controller,
and then set the data of CODE No. [5d] to "0000"
in "Setup of external static pressure" on this page.
4
5
6
).
3
.
4
, select a
– 23 –
Installation Manual
SW501-1
SW501-2
MCU(IC501)
SW501-1
0000
OFF
0001
ON
0003
OFF
0006
ON
SW501-2
OFF
OFF
ON
ON