Technical Data
Power circuit
Operating voltage DC U
B
Rated power
Residual ripple U
SS
Inrush current, I
peak
Operating voltage AC U
B
Rated power
Nominal frequency
Inrush current, I
peak
Fuse, internal
Isolation between supply circuit / control circuit
Control circuit
Rated output voltage (S11 to S21), short-circuit protected
Inputs (S12/S22, S32, S14, S34, Y2, Y40)
U
, High
e
U
, Low
e
I
, High
e
I
, Low
e
Input capacity
Line resistance
Line capacity
Times
OFF time t
(K1, K2 and K5)
R
Release delay time t
(K3, K4), tolerance
RV
0.1 to 3 s
0.1 to 30 s
0.1 to 300 s
Response time t
A
Ready time t
B
Minimum activation time t
M
Recovery time t
W
Discrepancy time t
D
permitted test pulse time t
TP
permitted test frequency
Output circuit
Enabling paths
Contacts
Rated switching voltage U
n
max / min current I
per current path
n
fuse
max. total current of all current paths
Utilisation category according to DIN EN 60947-5-1
Mechanical service life (switching mechanisms)
General data
Air gap / creepage paths between the circuits
Pollution degree / Rated surge voltage
Rated voltage
Contamination level of the device: inside / outside
Protection class according to DIN EN 60529 Case / terminals
Ambient / storage temperature
Weight
Terminals and connection data
Single-core or finely stranded
Finely stranded with wire-end ferrule acc. to DIN 46228
AWG
Max. tightening torque
Stripping length
LED
Colour
SUPPLY
Green
Reset
Green
K1,K2
Green
K3,K4
Green
FLT
Red
6
SNV 4074SL
SNV 4076SL
DC device
AC device
View
On
On
Flashing 3 Hz
On
On
Flashing 1Hz
Flashing 3Hz
On
min
20.4 V DC
5 A
95 V AC
48 Hz
5 A
15 V
-5 V
-2.5 mA
0.1 / 0.2 / 0.3 / 0.4 / 0.5 / 0.8 / 1.0 / 1.5 / 2.0 / 3.0 s
0.1 / 2 / 4 / 6 / 8 / 10 / 15 / 20 / 25 / 30 s
0.1 / 20 / 40 / 60 / 80 / 100 / 150 / 200 / 250 / 300 s
300 ms
100 ms
50 ms
2 NO and 2 NC contacts not delayed, 2 delayed NO and 2 NC contacts
3 NO and 1 NC contacts not delayed, 3 delayed NO contacts
max. 6 A operating class gG (Use in combustion plant max 0.6 x I
according to DIN EN 60664-1
III / 4 kV (Basic insulation)
-25 to +55 / -25 to +75 °C
screw-type terminals
1 × 0.2–2.5 mm² / 2 × 0.2–1.0 mm²
1 × 0.25–2.5 mm² / 2 × 0.25–1.0 mm²
26–14
0.5–0.6 Nm (5–7 lbf-in)
Meaning
Supply voltage present
S14 on
S14 and S34 on
Relays K1 and K2 (and K5) on
Relays K3 and K4 on
Release delay time active (only for t
Internal error (self-monitoring)
Different from release delay time
typical
24 V DC
2.8 W
115-230 V AC
3.2 W / 6.3 VA
50-60 Hz
T 2 A
yes (AC 115 - 230 V)
22 V
24 V
0 V
3 mA
10 nF
0.1 % ± 15 ms
1 s
230 V AC
6 A / 5 mA (24V)
See Diagram 1
AC-15: Ue 230 V, Ie 3 A
DC-13: Ue 24 V, Ie 3 A
6
10x10
300 V AC
2 / 3
IP 40 / IP 20
0.33 kg
0.35 kg
spring-type terminals
1 × 0.2–1.5 mm²
1 × 0.25–1.5 mm² (trapezoid crimping)
24–16
max. 7 mm
> 3s)
RV
max
26.4 V DC
2.4 V
253 V AC
62 Hz
40 V
30 V
5 V
4.5 mA
2.1 mA
70 Ω
200 nF
20 ms
200 ms
1 ms
-1
10 s
)
n