Descargar Imprimir esta página

Siemens PolyCool Superheat CPS 40 Manual De Instalación Y Servicio página 39

Ocultar thumbs Ver también para PolyCool Superheat CPS 40:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Picture Function
16
Manipulated EIV
opening degree
17
EIV actual
position
feedback to the
manipulated
opening
18
Actual value
display
Building Technologies
HVAC Products
Simulation mode / SIMU
(Continue with <OK> / picture 15)
Parameter
Code
Setpoint *
MAN EIV 0...10 V /
DC 0...10 V
signal
DC 0...10 V
MAN EIV
signal
EIV
0...100 %
opening
Evaporation
TO
temperature
Suction gas
TOH
temperature
Continously press <ESC> to exit
* Caution! At your own risk!
1) In the simulation mode, the monitoring functions are
deactivated if not enabled via D1. Therefore, your plant
could be seriously damaged.
2) In the simulation mode, the monitoring functions can be
deactivated on purpose (through D1). This allows the
plant to be manually operated for about 15 minutes.
CPS40
Adjustable
Settings
range
Default
0.0 V
0.1 V
-
-
-
-
CE1U3372XX / H 74 319 0555 0 a
Procedure
Set parameter
/ value with +/-
Confirm with
<OK>
Back to
regulation
mode with
<ESC>
39/124
22.09.2006

Publicidad

loading