7.5. INSTALLATION OF THERMOSTAT OR TEMPERATURE SENSOR (CHANGE OVER)
7.5.1. TRM-FA OR TRM-VP
The thermostat (change-over switch) supplied is to be
mounted on the water supply pipe.
7.5.2. TAE20 OR AQUANET OR AQUASIMP
The temperature sensor (change over) supplied is to be
fitted to the water inlet tube.
Before assembling the change over sensor, coat the tube
with heat conducting paste to guarantee that the real
temperature is recorded.
The M and B2 change over sensor inputs can be
connected to the mains power supply. If it is necessary to
extend the sensor wires, ensure that wires appropriate for
this voltage are used.
8. AERAULIC CONNECTIONS
Only the supply air is insulated.
The unit is fitted with a pre-cut inlet for fresh air intake:
²
Ø100mm or Ø125mm
In no event should one or more of the apertures be blocked.
If one of these apertures were to be blocked, it would create a drop in unit available
static pressure, and poor air irrigation on the coil surface, leading to a significant drop
in unit performance and possible fan motor damage.
8.1. DUCT CONNECTION DIMENSIONS
DUCTYS
DUCTYS
SEE APPENDIX
11
TAE20: SCH
AQUANET: WPT
AQUASIMP: WPT