Installation
Turn the detector by the base, incor-
porates double-sided adhesive tape
so that it can stick on any surface.
Installation of cells:
Smoke, heat and burned particles are
generally raised to the ceiling, so the
most advisable option is to install the
smoke detector in the center of it.
Please keep at least 30 cm distance
between the sensor and the lamps or
decoration, and a distance of at least
15 cm from the wall and / or corners.
Install the detector on the sides of the
aisle if it has a length equal to or
greater than 12 meters.
Tilt roof installation:
Please install the detector 90 cm away
from the center of the roof.