IC logic= 0 - Input configured as Start E. Operation according to STEP-BY-STEP MOV. logic.
IC logic= 1 - Input configured as Start I. Operation according to STEP-BY-STEP MOV. logic.
IC logic= 2 - Input configured as Open.
The command causes the leaves to open. If the input stays closed, the leaves stay open until the contact is opened. When the contact is open, the automated device closes following
the TCA time, where activated.
IC logic= 3 - Input configured as Closed.
The command causes the leaves to close.
IC logic= 4 - Input configured as Ped.
The command causes the leaf to open to the pedestrian (partial) opening position. Operation according to STEP-BY-STEP. logic
IC logic= 5 - Input configured as Timer.
Operation same as open except closing is guaranteed even after a mains power outage.
IC logic= 6 - Input configured as Timer Ped.
The command causes the leaf to open to the pedestrian (partial) opening position. If the input stays closed, the leaf stays open until the contact is opened. If the input stays closed and
a Start E, Start I or Open command is activated, a complete opening-closing cycle is performed before returning to the pedestrian opening position. Closing is guaranteed even after a
mains power outage.
SAFE logic= 0 - Input configured as Phot (photocell). (fig.F, ref.1).
Enables connection of devices not equipped with supplementary test contacts. When beam is broken, photocells are active during both opening and closing. When beam is broken
during closing, movement is reversed only once the photocell is cleared. If not used, leave jumper inserted.
SAFE logic= 1 - Input configured as Phot test (tested photocell). (fig.F, ref.2).
Switches photocell testing on at start of operation. When beam is broken, photocells are active during both opening and closing. When beam is broken during closing, movement is
reversed only once the photocell is cleared.
SAFE logic= 2 - Input configured as Phot op (photocell active during opening only). (fig.F, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during closing. During opening, stops
motion for as long as the photocell beam stays broken. If not used, leave jumper inserted.
SAFE logic= 3 - Input configured as Phot op test (tested photocell active during opening only (fig.F, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during closing. During opening, stops motion for as long as the photo-
cell beam stays broken.
SAFE logic= 4 - Input configured as Phot cl (photocell active during closing only). (fig.F, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during opening. During closing, move-
ment is reversed immediately. If not used, leave jumper inserted.
SAFE logic= 5 - Input configured as Phot cl test (tested photocell active during closing only (fig.F, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during opening. During closing, movement is reversed immediately.
SAFE logic= 6 - Input configured as Bar (safety edge). (fig.F, ref.3).
Enables connection of devices not equipped with supplementary test contacts. The command reverses movement for 2 sec.. If not used, leave jumper inserted.
SAFE logic= 7 - Input configured as Bar (tested safety edge (fig.F, ref.4).
Switches safety edge testing on at start of operation. The command reverses movement for 2 sec.
SAFE logic= 8 - Input configured as Bar 8k2 (fig.F, ref.5). Input for resistive edge 8K2.
The command reverses movement for 2 sec..
6) SAFETY DEVICES
Note: only use receiving safety devices with free changeover contact.
6.1) TESTED DEVICES Fig. F
6.2) CONNECTION OF 1 PAIR OF NON-TESTED PHOTOCELLS FIG. C
7) CALLING UP MENUS: FIG. 1
7.1) PARAMETERS MENU (PARA ) (PARAMETERS TABLE "A")
7.2) LOGIC MENU (LOGIC) (LOGIC TABLE "B")
7.3) DEFAULT MENU (default)
Restores the controller's DEFAULT factory settings. Following this reset, you will need to run
the AUTOSET function again.
7.4) LANGUAGE MENU (language)
Used to set the programmer's language on the display.
7.5) AUTOSET MENU (AUTOset)
• Launch an autoset operation by going to the relevant menu.
• As soon as you press the OK button, the ".... .... .... " message is displayed and the control unit
commands the device to perform a full cycle (opening followed by closing), during which the
minimum torque value required to move the leaf is set automatically.
During this stage, it is important to avoid breaking the photocells' beams and not to use the
START and STOP commands or the display.
Once this operation is complete, the control unit will have automatically set the optimum
torque values. Check them and, where necessary, edit them as described in the programming
section.
Warning!! While the autoset function is running, the obstacle detection function is not
active. Consequently, the installer must monitor the automated system's movements
and keep people and property out of range of the automated system.
TABLE "A" - PARAMETERS MENU - (PARA )
Parameter
min.
max.
Default
0
120
TCA
partial
1
99
opening
1
99
OP. F ORCE
1
99
CLS. F ORCE
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
INSTALLATION MANUAL
Command input configuration
Safety input configuration
Personal
Definition
10
Automatic closing time [s]
40
Partial opening [%]
Leaf force during opening
80
[%]
Leaf force during closing
80
[%]
https://appceso.com
7.6) LIMIT SWITCH ADJUSTMENT MENU (L. S W ADJ) (Fig . D)
Limit switch adjustment procedure:
1) Go to L.SW ADJ and confirm with OK.
2) The display reads CLOSE. Use the UP and DOWN keys to move the door to the closing limit switch
position. Confirm with OK. The display reads PRG.
3) If prompted by the display, turn the adjustment ring: anticlockwise if the display reads UP; clock-
wise if the display reads DOWN. Once you have reached the correct position, the display reads
OK. Confirm with the OK key. The display reads PRG.
4) The display reads OPEN. Use the UP and DOWN keys to move the door to the opening limit switch
position. Confirm with OK. The display reads PRG.
If the display reads KO, it means adjustment was not successful.
This may be caused by:
- the ESC key being pressed before adjustment was completed
- stored travel being too short
7.7) STATISTICS MENU
Used to view the version of the board, the total number of operations (in hundreds), the
number of transmitters memorized and the last 30 errors (the first 2 digits indicate the
position, the last 2 give the error code). Error 01 is the most recent.
8) OPEN IN OTHER DIRECTION (Fig. D1)
9) CONNECTION WITH EXPANSION BOARDS AND UNIVERSAL HANDHELD PROGRAMMER
VERSION> V1.40 (Fig. B) Refer to specific manual.
10) RADIO-RECEIVER (Fig. B)
The board comes ready for connection of removable radio-receiver.
The receiver's channel 1 controls input IC1.
The receiver's channel 2 controls terminals 26-27.
WARNING! Incorrect settings can result in damage to property and injury to people and animals.
WARNING: Check that the force of impact measured at the points provided for
by standard EN 12445 is lower than the value laid down by standard EN 12453.
For best results, it is advisable to run the autoset function with the motors idle (i.e. not over-
heated by a considerable number of consecutive operations).
Waiting time before automatic closing.
Adjusts partial opening percentage compared to total opening in "Partial open" mode.
Force exerted by leaf/leaves during opening. This is the percentage of force delivered, beyond the force
stored during the autoset cycle (and subsequently updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current safety
requirements are met with the set value (*). Install anti-crush safety devices
where necessary.
Force exerted by leaf/leaves during closing. This is the percentage of force delivered, beyond the force
stored during the autoset cycle (and subsequently updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current safety
requirements are met with the set value (*). Install anti-crush safety devices
where necessary.
Description
LEO B CBB 3 400 W 01-
13