3.7 ELECTRICAL WIRING
Main switch
230V ~ 50Hz
Fig. 8
A
20016967
ATTENTION:
Do not swap neutral and phase over, follow the diagram shown
carefully and carry out a good earth connection.
The section of the conductors must be at least 1mm². (Unless requested
otherwise by local standards and legislation).
The electrical wiring carried out by the installer must be in compli-
ance with the rules in force in the country.
TESTING
Check the burner has stopped by opening the thermostats.
Check that the burner is blocked while is working by opening the connector
(CN1) inserted in the probe red wire and located outside the control box.
CONTROL BOX, (see fig. 8)
To remove the control box from the burner it is necessary to:
disconnect all the connectors, the 7-pin plug, the high voltage cables and the
earth wire (TB);
unscrew the bolt (A, fig. 8) and pull the control box in the direction of the ar-
row.
To install the control box it is necessary to:
screw the bolt (A) in at a torque of 1 - 1.2 Nm;
reconnect all the connectors previously disconnected.
NOTES
The burners have been type-approved for intermittent operation. This means they
must stop at least once every 24 hours in order to allow the electrical control box
to check its efficiency on start-up. The boiler limit thermostat (TL) normally en-
sures the burner halts. If this does not happen a time switch halting the burner at
least once every 24 hours must be applied in series to limit thermostat (TL).
E9250
KEY TO LAY-OUT
C
CN1 – Ionisation probe connector
E
h1
MV – Motor
PA
PG
RS
SO
S3
T6A – Fuse
TB
TL
TS
V10 – Safety valve
V11 – Adjustment valve
X..
XP.. – Socket
D4626
8
GB
– Capacitor
– Electrode
– Hour counter
– Min. air pressure switch
– Min. gas pressure svitch
– Remote reset
– Ionisation probe
– Lock-out signal (230V - 0.5A max.)
– Burner-earth
– Limit thermostat
– Safety thermostat
– Plug
CARRIED-OUT
IN THE FACTORY
TO BE DONE BY
THE INSTALLER