Warning And Error Messages During Operation - BONFIGLIOLI Vectron ACTIVE Serie Guia De Inicio Rapido

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6.1

Warning and error messages during operation

The code which can be read out via parameter
messages. For example, code A0088 signals the individual warning messages A0008 + A0080.
Code
A0000
No warning message available.
A0001
Frequency inverter overloaded, warning code (A0002 or A0004)
A0002
Frequency inverter overloaded (60 s), check load behavior.
A0004
Short-term overload (1 s), check motor and application parameters.
A0008
Max. heat sink temperature reached, check cooling and fan.
A0010
Max. inside temperature reached, check cooling and fan.
A0020
Speed reference value is limited by a controller.
A0080
Max. motor temperature reached, check motor and sensor.
A0100
Mains phase failure, check mains fuses and supply cable.
A0400
Limit frequency reached; output frequency is limited.
A4000
DC link voltage has reached the type-specific minimum.
The error code saved after a fault in parameter
error diagnosis. The error message is to be acknowledged via the keys of the control unit and
digital input S1IND.
Code
F00
00
No fault has occurred.
F01
02
Frequency inverter overloaded (60 s), check load behavior.
03
Short-term overload (1 s), check motor and application parameters.
F02
00
Heat sink temperature too high, check cooling and fan.
01
Temperature sensor defective or ambient temperature too low.
F03
00
Inside temperature too high, check cooling and fan.
01
Inside temperature too low, check electrical cabinet heating.
F04
00
Motor temperature too high or sensor defective, check connection S6IND.
03
Phase failure, check motor and wiring.
F05
00
Overloaded, check load situation and ramps.
03
Short circuit or earth fault, check motor and wiring.
05
Asymmetric motor current, check motor and wiring.
06
Motor phase current too high, check motor and wiring.
07
Message from phase monitoring, check motor and wiring.
F07
00
DC link voltage too high, check deceleration ramps and connected brake resistor.
01
DC link voltage too low, check mains voltage.
02
Power failure, check mains voltage and circuit.
03
Phase failure, check mains fuses and circuit.
04
Mains voltage UDC too high on switch-on, check voltage.
05
Mains voltage BC too high on switch-on, check voltage.
06
Mains voltage MC too high on switch-on, check voltage.
34
34
Warnings
Warning messages
Meaning
Last Error
Error messages
Meaning
Overload
Heat sink
Inside temperature
Motor connection
Output current
DC link voltage
269 can be composed of several
310 facilitates troubleshooting and
06/07
06/07

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Act 201Act 401

Tabla de contenido