Installation Instructions – Commercial Recessed Compact
Fluorescent-Emergency
Instructions d'installation - Ampoule fluorescente compacte
encastrée d'urgence commerciale
Instrucciones de instalación de la luminaria fluorescente de
emergencia compacta, empotrada y de uso comercial
IMPORTANT: Read carefully before installing fixture. Retain
for future reference.
INSTALLATION
1.
To prevent electrical shock and unintentional battery
discharge, do not join the unit connector until
the installation is complete. Immediatly prior to
premanently turning the A.C. Power on, engage the
connector within the single gang switch box.
SERVICING
1.
This fixture provides more than one power supply
output source. To reduce the risk of electrical shock,
disconnect both normal and emergency sources by
turning off the A.C branch circut and by disconnecting
the connector on the charge indicator/test switch
assembly.
2.
The emergency source requires an unswitched A.C
power source of either 120 or 277 volts. Properly cap
the unused A.C. lead. Refer to wiring diagram.
3.
This unit is for recessed ceiling mounting only. Do not
use outdoors, in hazardous locations, nor near gas or
electrical heaters.
4.
This is a recessed ceiling mounted compact
fluorescent unit, with standby battery operation. In
the normal mode, lamp will be illuminated. In the
emergency mode, one lamp will provide emergency
illumination for a minimum of 90 min. In accordance
with U/L standrad #924. The test switch and indicator
light are provided for ceiling mounting near the fixture
in a single gang switch box (provided).
5.
When used in insulated ceilings, insulation must be
kept off the unit and no closer than 3"from the unit on
all sides.
Brand Logo
reversed out of
black
SAFETY: When Using Electrical Equipment, basic saftey
precautions should always be followed, including The
following:
6.
Do not use this equipment for other than the
intended use.
7 .
Install only in accordance with National Electrical
Code and Local Regulatory Agencies requirements.
8.
Installation and servicing to be performed only by
qualified personnel.
Figure 1.
Standard Installation
Figure 2.
TM
INS #
INS #
INS #