Sensor de energía eNet, enchufable
Transmit current
Transmit effective power
Transmit reactive power
Transmit apparent power
Transmit absolute active
energy
Transmission interval
Rel. threshold value, effective
power
Abs. threshold value, effective
power
Suppression length, effective
power
82582213
J0082582213
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
On, Off
Basic setting: On
1 ... 60 min
Basic setting: 15 min
1 ... 50 %
Basic setting: 10 %
0 ... 2000 W
Basic setting: 1 W
0 ms ... 300 s
Basic setting: 0 ms
5/7
Transmits the current current
value.
Transmits the average effecti-
ve power. If negative values
are displayed, then effective
power is fed in, e.g. via a pho-
tovoltaic system.
Sends the current fundamen-
tal oscillation idle power value.
If negative values are displa-
yed, this is capacitive reactive
power. Positive values show
an inductive reactive power.
Transmits the current appa-
rent output value.
Transmits the cumulative va-
lue of the active energy. If ne-
gative values are displayed,
then effective energy is fed in,
e.g. via a photovoltaic system.
The current consumption data
is transmitted at the interval
set here at the latest. Changes
to the effective power cause
fresh transmission, however
only after one minute at the
earliest.
The transmission of the con-
sumption data can be coupled
to the change in effective po-
wer. The basis is always the
most recently transmitted ef-
fective output value. If the per-
centage change entered here
is exceeded, then all the mea-
sured values are resent.
A lower threshold value of the
effective power can be ente-
red here, to avoid frequent
transmission in the lower po-
wer range. Event-controlled
transmission is only active
above this threshold value.
Triggers for event-controlled
transmission are often switch-
on and switch-off operations.
In order to avoid incorrect
measured values due to
switch-on peaks, this parame-
ter can be used to enter a sup-
pression period. The measu-
red values are only transmit-
ted if the effective power is still
above or below the relative th-
reshold value after the set ti-
me.
10.04.2017