Lenze E94AZRP0824 Instrucciones Para El Montaje página 43

Filtro rf
Ocultar thumbs Ver también para E94AZRP0824:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Environmental conditions
Climate
Storage
Transport
Operation
Site altitude
Pollution
Vibration resistance
Transport
Operation
Mounting conditions
Mounting place
Mounting position
Free spaces
Dimensions
Weights
EDK94AZRP45 DE/EN/FR/ES/IT 5.0
General data and operating conditions
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Current derating at +45 ... +55 °C: 2.5 %/°C
0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of
5 %/1000 m
EN 61800-5-1
Pollution degree 2
2
(9.81 m/s
= 1 g)
IEC/EN 60721-3-2 2M2
EN 61800-2
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
200 ... 500 Hz: acceleration resistant up to 15 m/s
Germanischer
5 ... 13.2 Hz: amplitude ±1 mm
Lloyd
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068-2-6 10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g
In the control cabinet
Vertical
Technical data
47
4
2
2
43