Wiring
WARNINGS:
• Open SITRANS LPS200 only when supply voltage is switched off.
• Select correct voltage using manual voltage jumper before switching
on the power supply.
Notes:
All field wiring must have insulation suitable for at least 250 V AC.
A disconnect switch shall be in close proximity to the equipment and within easy
reach of the operator.
Unused cable conduit fittings must be locked with a closing element or plug.
Commissioning must be done only with a closed device.
Observe all pertinent rules and regulations of the country of installation.
European Standards
When mounting SITRANS LPS200 in hazardous areas, make sure the customer-
supplied cable gland and/or plugs are certified ATEX 100a flameproof. The
temperature range must be at least –20 to 80 °C (–4 to 176 °F). The minimum
ingress protection requirement of IP6x according to European Standard EN 60529
must be satisfied. Observe special conditions for safe use of the cable gland as
described by the gland's approval documentation.
The requirements of European Standard EN 50281-1-2 regarding dust deposits and
temperatures must be followed.

Voltage Selector

Select the voltage by placing the voltage jumper over the pins as illustrated below.
7
6
5
7ML19985FS61
lamp
1
2
protective earth
terminal
SITRANS LPS200 – INSTRUCTION MANUAL
voltage
jumper
24 V
115 V
230 V
Page EN-9