Honeywell SONIK Guia De Inicio Rapido página 8

Tabla de contenido

Publicidad

Mode with
Colour
Bluetooth
connected
Fault
Yellow
Inhibit
Yellow
Warning
Yellow
Normal
Blue
Normal
Blue
Alarm
Red
Over-range
Red
Connecting
Blue
Connected
Blue
mA Loop Status Signaling
Mode
Default Value (mA)
Discrete Mode
Fault
Inhibit
Warning
Normal
4
Pre-alarm
16
Alarm
20
Over-range
Periodic Proof Test
Searchzone Sonik functionality can be verified using the Searchzone Sonik Test Unit (optional) in
combination with the Mobile App.
CAUTION
While operating the Searchzone Sonik Test Tool, ultrasound is generated. Do NOT aim the tool towards
your or anyone else's body or head.
The Searchzone Sonik Test Unit generates two different test signals to check detector's functionality:
1) the first test signal is recognized by detector as a gas leak. It is reported through change in detector's
LED ring status indicator. The test is automatically logged.
2) the second test signal is used for end-to-end testing. It is reported through detector's LED ring status
indicator, Relays and through 4-20 mA loop to indicate alarm condition. The test is automatically logged.
Refer to Maintenance section of Technical Manual for instructions on how to perform LOCAL and END-
to-END test using the Searchzone Sonik Test Unit.
Refer to Mobile App section of Technical Manual for instructions on how to access proof test readings.
You can download Technical Manual from www.honeywellanalytics.com
Flashing
Yes
No
Yes
No
Yes
Yes
Yes
Yes
No
Min Value (mA)
Proportional Mode
1
0
2
1
3
1
Proportional to sound
4
pressure level
Not available
4
Not available
4
21
20
Default Scheme
Default
Default
Default
Default
Optional
Default
Default
Default
Default
Max Value (mA)
3.6
3.6
4
20
20
20
22
8

Publicidad

Tabla de contenido
loading

Tabla de contenido