Royal BETTY THERMO Manual De Instalación Y Mantenimiento página 25

Ocultar thumbs Ver también para BETTY THERMO:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

UNI 10683/98 – Chimney tops, distances and
positioning, Roof slant; distance between the ridge
cap and chimney; minimum chimney height , less than
1,85 m; greater than 1,85 m; 0,50 m beyond the ridge
cap;1,00 m from the roof .
5.4
SMOKE OUTLET CONNECTION
with EN 13384-1.
• The SMOKE connection between the cooker and
• In order to connect the cooker to the chimney you may
perform maximum 3 changes of direction that should not
exceed 90°, the fume duct should not exceed 2 metres
in length and 3 metres in total (
• if the outlet is placed on the ceiling, make sure that the
the direction.
• Follow the indications in the technical data sheet
regarding the chimney draught value.
00 477 7250 -09/2018 - PN - Italy
INSTALLAZIONE
INSTALLAZIONE
Fig. 5.2.1
Fig. 5.2.2
).
.
Fig. 5.2.3
Fig. 5.2.4
Fig. 5.2.5
A
2,00 m
0,40 m
> 5 m
0,50 m
B
> A
A
asse del colmo
C
,
OMIGNOLI
DISTANZE E POSIZIONAMENTO
NO
5 m
B
0,50 m
UNI 10683/98
25

Publicidad

Tabla de contenido
loading

Tabla de contenido