Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

SP2 OPERATING MODES
(see page 6)
Function
Options
SP2.A [nonE]
dV.hi dV.Lo bAnd FS.hi FS.Lo Cool
Main SP2 operating mode
SP2.b [nonE]
LtCh hoLd nLin
Subsidiary SP2 mode: latch/sequence
Non-linear cool proportional band
INPUT SELECTION AND RANGING
dI.SP [1]
0.1
Select display resolution: for display of process temperature, setpoint, OFSt, Set.2, hi.SC,
LoSC.
hi.SC sensor minimum [sensor maximum]
°C/°F
Set full scale
Lo.SC [sensor minimum] sensor maximum
°C/ºF
Set scale minimum (default 0°C or 32°F)
inPt
Select input sensor [nonE]
(See SENSOR SELECTION table, page 11)
unit [nonE]
°C °F bAr Psi Ph rh SEt
Select °C/°F or process units

LEVEL 3

LEVL 3
OUTPUT CONFIGURATION
Note: 'Read only' after initial configuration. rSET ALL full reset to factory settings required
to change SP1.d subsequently.
SP1.d [nonE]
rLY
SSd
rLY1 rLY2 SSd1
Select SP1 output device
SP2.d [nonE]
SSd rLY
rLY2 rLY1 SSd2
Read SP2 output device
(read only)
Dual Relay and Dual SSd output options are factory set.
8
Note: (when in initial configuration only)Hold
to or from output devices in shaded portion.
[Factory settings] shown in brackets
and
or
for 10 seconds to move
burn
Sensor burn-out/break protection
Caution: Settings affect fail safe state.
[uP.SC]
dn.SC
1u.2d
1d.2u
rEu.d
Select output modes: Direct/Reverse
Caution: Settings affect fail safe state.
[1r.2d]
1d.2d
1r.2r
1d.2r
Select Reverse on SP1 for heating and Direct for
cooling applications.
rEu.L
Select SP1/2 LED indicator modes
[1n.2n]
1i.2n
1n.2i
1i.2i
SPAn [0.0]
to ±25% sensor maximum
Sensor span adjust
For recalibrating to align readings with another instrument e.g. External Meter, data logger.
See Full Operating Manual (ADVANCED SETTINGS).
ZEro
[0.0]
to ±25% sensor f/s
Zero sensor error (see Sensor span adjust above).
ChEK
[oFF]
on
Select control accuracy monitor
rEAD
[ Var]
hi
Lo
Read control accuracy monitor
[ Ct A]
tECh
CT b
Ct 1
Ct 2
Ct 3 Ct 4
Read Autotune tuning cycle data (see Operating Manual)
UEr
Software version number
rSET
[nonE]
ALL
Resets all functions to factory settings
Caution: This selection will lose all of the current settings.
SP1
SP2
Upscale
Upscale
Downscale
Downscale
Upscale
Downscale
Downscale
Upscale
SP1
SP2
Reverse
Direct
Direct
Direct
Reverse
Reverse
Direct
Reverse
SP1
SP2
Normal
Normal
Invert
Normal
Normal
Invert
Invert
Invert
oS 1
uS
oS 2

Publicidad

Capítulos

Tabla de contenido
loading