Typical Applications (cont'd)
Telephone Pedestal
Ground Bar
Sheath Connection
Ground Level
Ground Bar
Sheath Connection
Ground Level
Above Telephone Space
Ground wire doubled
under ground clamp
12
Phone
Pedestal
Ground Rod
Phone
Pedestal
Ground Rod
Note: Clamp onto the ground
conductor (as shown) or onto the
ground rod.
1
2
Note: Clamp onto the ground conductor
(as shown). The reading will indicate the
connection between the telephone circuit
ground and the power utility ground.
1.
Remove ground bar connection
to pedestal rod.
2.
Extend pedestal rod lead to the
ground bar using a temporary
jumper.