5.1 Technical specifications

Electrical characteristics

I/T network and industrial operating modes
Overload, and Bypass
AC source in tolerance.
Overload, and Bypass
AC source not in
tolerance.
Output short circuit and
Bypass AC source in
tolerance.
Output short circuit
and Bypass AC source
not in tolerance.
Selection of protection devices
UPS unit with common Normal and Bypass AC inputs
Bypass AC
Normal AC
UPS unit with separate Normal and Bypass AC inputs
Bypass AC
Normal AC
When sizing the upstream circuit breakers, the parameters presented below must be taken into account:
Line current values
power rating
7 kVA
11 kVA
Discrimination of upstream/downstream protections mentioned in paragraph 2.6 is achieved for a 30 m
cable length and 10 mm² cross section.
Circuit breaker capacity must be selected according to the installation, length and cross section of cables.
Industrial mode
Same as I/T network mode, but the UPS
does not return to normal mode if overload
released.
Load is transfered to Bypass AC source
with 10 milliseconds output break. The
UPS does not return to normal mode if
overload released.
Load is transfered to Bypass AC source,
the UPS returns to normal mode if the
short circuit is released by downstream
circuit breaker action (see section 2.6).
The load is transfered to Bypass AC
source with 10 milliseconds output break.
The UPS does not return to normal mode
if the short circuit is released by
downstream circuit breaker action
(see section 2.6).
Upstream
circuit breaker
(not supplied)
Upstream
circuit breaker
(not supplied)
Upstream
circuit breaker
(not supplied)
UPS
Continuous current
at 230/160 Volts
and nominal load
23/33 A
38/54 A
11
Input
fuse
10
Q1
11
Input
fuse
10
Q1
Continuous current
at 160 Volts and
overload = 110 %
limited to 2 minutes
37 A
60 A

5. Appendices

I/T network mode
Load is transfered to Bypass AC
source. UPS returns to normal mode
if overload released
The UPS shuts down and load is not
transfered to Bypass AC source.
The load remains powered by the
UPS. The UPS shuts down after
3 minutes if the short circuit remains.
The load remains powered by the
UPS. The UPS shuts down after
3 minutes if the short circuit remains.
Downstream
Output
circuit breaker
fuse
(not supplied)
8
Downstream
Output
circuit breaker
fuse
(not supplied)
8
Input fuse rating
Output fuse rating
80 A
100 A
34007558EN/AE - Page 35
80 A
100 A