Installing The Indoor Unit - York JBK 50 BGY Instrucciones De Instalación

Unidades split cassette bomba de calor
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 7
Locating indoor unit
1. Do not place objects near the air dis-
charge so the air may be distributed
throughout the room.
2. Make sure the indoor unit is installed
firmly and in horizontal position.
3. Select a location that can support 4
times the weight of the unit so as to de-
crease noise level due to vibration.
4. Select a location where it is easy to in-
stall the drain, and as close to the out-
door unit as possible.
5. Make sure there is sufficient clearance
for all maintenance servicing.
6. Make sure the suspension system can
support 4 times the weight of the unit so
as to avoid saturation (permanent com-
pression).
Note:
1. Keep a reasonable distance from the
kitchen.
2. This equipment should not be installed
in laundry rooms.
Opening in the ceiling and sus-
pension bolts (M10)
JBK 50 BGY
400 FASTENING
600 INDOOR UNIT
650 FRONT PANEL
JBK 75, 100, 120 BGY
780 FASTENING
840 INDOOR UNIT
890 OPENING IN THE CEILING
950 FRONT PANEL
Fig. 3
14
CEILING

Installing the indoor unit

and 4a)
(Fig. 3 and 3a)
1. Locate the indoor unit.
-
Fasten the support to the fastening bolts.
Make sure they are firm and use nuts
and washers on both top and bottom of
the support. The fastening plate or fas-
teners (1) avoid movement of the wash-
ers.
-
Use template (2) to establish the dimen-
sions of the opening in the ceiling.
-
The centre of both the opening in the
ceiling as well as the unit are indicated
on the template supplied with this equip-
ment.
-
Fasten the template to the indoor unit
with screws (3) x 3.
2. Locate the unit in correct position for in-
stallation.
3. Make sure the unit is in horizontal posi-
tion (with a level).
-
The indoor unit is equipped with a pump
A
and float at each one of the four corners.
Check correct positioning with a level or
vinyl pipe. (If the unit is installed con-
trary to condensed water flow, the float
will not operate correctly and could
cause water spilling.)
4. Remove the fastener from washers (1)
and screw in the top nut.
5. Remove the installation template (2).
A
FASTENING
VIEW FROM "A"
> 20
950
Fig. 3a
(Fig. 4
M10 BOLT
WASHER (INCLUDED)
TIGHTEN WITH
TWO NUTS
FASTENING
SUPPORT
Fig. 4
GB
INSERT
WASHER
FASTENER (1)
WATER
LEVER
VINYL PIPE
CENTRE OF OPENING
POSITION CORNERS
IN THE CEILING
OF DRAIN SYSTEM
BOLTS IN THE
SCREWS (3)
SCREWS (3)
Fig. 4a
Attention: Tighten the nuts to make sure
the unit does not fall.
Cooling connections (Fig. 5)
- Use both wrenches at the same time, as
shown in the following illustrations, to con-
nect and disconnect the cooling pipes.
- See Table 1 to determine correct torque
to be applied to the nuts. (Tightening in
excess could cause gas leaks.)
- When connecting pipes, cover both the
outer as well as inner sides of the pipes
with cooling machine oil, and tighten them
manually 3 or 4 turns.
- Check pipe connections for gas leaks, and
lay them as indicated below.
- Use the sealing filler (11) to insulate con-
nection (8).
INSTALLATION
TEMPLATE (2)

Publicidad

Tabla de contenido
loading

Tabla de contenido