Water connections
Pipe water content
Internal Diameter
Outer diameter
12 mm
14 mm
16 mm
copper
20 mm
25 mm
32 mm
"12.7 mm (1/2'')"
"16.3 mm (5/8'')"
steel
"21.7 mm (7/8'')"
"27.4 mm (11/16'')"
% Inhibited
Ethylene
Freezing time (*)
Capacity
Correction
Absorbed power
Factors
Loss of head
(*) Note: Temperature values are indicative.
Always refer to the temperatures indicated for the specific product used
TABLE TO USE FOR CALCULATING THE WATER CONTENT IN THE SYSTEM
Installed Unit
Unit content (*)
Pipe content (**)
Uses (fan-coil, panels, radiators, etc.) (***)
Total content (****)
(*) Consult the technical data table
(**) Consult the pipe water content table
(***) Consult the manual for the installed uses
(****) The water content of the system must be between the minimum and maximum values for the units with hydronic
kit and greater than the minimum value for units without hydronic kit. The minimum value is necessary to provide optimal
comfort.
For units without hydronic kit, add a suitable expansion vessel to the water content of the system.
Recommended water diagram
Typical water circuit diagram for unit 30AWH__X
(see fig. 12)
1
shut-off valves
2 line filter for water (10 mesh/inch)
3
pressure gauges
4 filling valve
5
system drain valve
(at the lowest points of the circuit)
6
air flushing valve
(in the highest parts of the circuit)
7
3-way valve
8
sanitary water accumulation tank
9
inside system
10 water circulation pump
11 expansion vessel
Do not use the heat pump to treat industrial process, swimming pool or sanitary water.
In all these cases, provide an intermediate heat exchanger.
Liters / meter
14 mm
0,11 l/m
16 mm
0,15 l/m
18 mm
0,20 l/m
22 mm
0,31 l/m
28 mm
0,49 l/m
35 mm
0,80 l/m
3/8'' Gas
0,13 l/m
1/2'' Gas
0,21 l/m
3/4'' Gas
0,37 l/m
1' Gas
0,59 l/m
10%
Glycol
-4 °C
0,996
0,990
1,003
Unit
Nominal water flow
Water content
system unit with
expansion vessel
Working pressure
Filling pressure
Difference in level
with unit at lowest level
20%
30%
-9 °C
-15 °C
0,991
0,983
0,978
0,964
1,010
1,020
l
l
l
l
Typical water circuit diagram for unit 30AWH__H
(see fig. 13)
1
shut-off valves
2 line filter for water (10 mesh/inch)
3
pressure gauges
4 filling valve
5
system drain valve
(at the lowest points of the circuit)
6
air flushing valve
(in the highest parts of the circuit)
7
3-way valve
8
sanitary water accumulation tank
9
inside system
30AWH
006_ 008_ 012_
Std
l/s
0,28
0,33
0,58
Min
l
21
28
42
Max
l
65
65
95
Max kPa 300
300
300
Min
kPa 120
120
120
Max
m
20
20
20
40%
-23 °C
0,974
1,008
1,033
.............
.............
.............
.............
.............
(Fig. 12/13)
30AW
7