5.0 TECHNICAL CHARACTERISTICS

Locking ringing at first power supply
Power supply nominal voltage .............................................................. 24 Vdc
Operation minimum voltage: ................................................................ 18 Vdc
Operation maximum voltage: ............................................................... 30 Vdc
Absorption at rest: ............................................................................... 24 mA typical
Battery recharge max absorption: ....................................................... 650 mA
Absorption in alarm conditions: .......................................................... 1A at nominal voltage
Power max in alarm conditions: .......................................................... 24W
Incandescent lamp power: ................................................................... 10W
Certified (EN 60529) shell protection grade: ......................................... IP33C
Shell protection grade as declared by manufacturer:............................ IP43
IK mechanical resistance grade as declared by manufacturer: ............. IK08
Operating frequency:............................................................................ 2400÷2800 Hz
Allocable battery: ................................................................................. 12V 1.9Ah, 12V 2Ah, 12V 2.1Ah
Certified operation temperature: ........................................................... -25 °C ÷ +70°C
End of line control R relay contact capacity .......................................... 6 A @ 24 Vdc
Dimensions (w x h x d) : ....................................................................... 212 x 270 x 78 mm
Angle
With battery
Without battery
Angle
With battery
Without battery
ACOUSTIC EMISSION SPECTRUM AT 1 METRE
SPETTRO EMISSIONE ACUSTICA AD 1 METRO
HPA700F – HORIZONTAL PLAN [ dB(A) ] at 1m.
15°
45°
100
105
100
105
HPA700F – VERTICAL PLAN [ dB(A) ] at 1m.
15°
45°
100
106
100
105
IMPORTANT: Batteries must be deemed dangerous wastes
(E.W.C. 160601) and therefore they must be delivered to
authorised disposal operators.
75°
105°
109
110
109
110
75°
105°
108
108
107
109
19/28
135°
165°
105
101
104
101
135°
165°
109
102
108
102