Descargar Imprimir esta página

Maintenance Instructions - Axis Communications A1001 Manual De Instalación

Controlador de puerta de red

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

AXIS A1001 Network Door Controller
1. Disconnect power from the product.
2. Press and hold the control button while reconnecting power. See .
3. Keep the control button pressed for 25 seconds until the status LED indicator turns
amber for the second time.
4. Release the control button. The process is complete when the status LED indicator turns
green. The product has been reset to the factory default settings. If no DHCP server is
available on the network, the default IP address is 192.168.0.90
5. Use the installation and management software tools, assign an IP address, set the
password, and access the product.
It is also possible to reset parameters to factory default through the web interface. Go to Setup >
Additional Controller Configuration > Setup > System Options > Maintenance and click Default.

Maintenance Instructions

To keep the access control system running smoothly, Axis recommends regular maintenance of the
access control system, including door controllers and connected devices.
Do maintenance at least once a year. The suggested maintenance procedure includes, but is not
limited to, the following steps:
Make sure all the connections between the door controller and the external devices
are secure.
Verify all the hardware connections. This requires access to the product's webpages. For
more information, see the User Manual.
Verify that the system, including the connected external devices, functions correctly.
-
Swipe a card and test the readers, doors, and locks.
-
If the system includes REX devices, sensors or other devices, test them as well.
-
If activated, test the tampering alarms.
If the results from any of the steps above indicate faults or unexpected behavior:
-
Test the signals of the wires using appropriate equipment and check if the
wires or cables are damaged in any way.
-
Replace all damaged or faulty cables and wires.
-
Once the cables and wires have been replaced, verify all the hardware
connections again. This requires access to the product's webpages. For more
information, see the User Manual.
Make sure all access schedules, doors, groups, and users are up to date. This requires
access to the product's webpages. For more information, see the User Manual.
If the door controller is not behaving as expected, see the User manual for information
about troubleshooting and the product's built-in maintenance functions.
For information about maintenance of the battery, see Requirements for Compliance with UL294
6th Edition on page 7 and Battery on page 10.
46

Publicidad

loading