Over Current Protection; Led Indicator - LEGRAND Wattstopper BZ-50 Manual De Instructions

Ocultar thumbs Ver también para Wattstopper BZ-50:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

BZ-50 Single load control
Neutral
White
BZ-50
120VAC
Black
Line
Power Pack
277VAC
BZ-50RC with sensor that has RJ45 jack
Neutral
White
BZ-50RC
Line
120VAC
Black
Power Pack
277VAC
RJ45 Connection
Low Voltage Input (Blue Wire for BZ-50, RJ-45 cable for BZ-50RC, Yellow Wire for BZ-50RC with FS-C2):
The low voltage input wire carries the +12-24VDC maintained input Control ON signal to the BZ-50. Applying 12-24VDC to this input
closes the BZ-50 load relay. Removing the voltage returns the relay to its normal state. This input is intended for sensor or control device
input.

Over Current Protection:

The BZ-50 contains built-in short circuit and thermal protection circuitry that shuts down the +24VDC output (red wire to sensors) to
prevent permanent damage to the power pack. Removing the excess load from the output restores the BZ-50 to proper operation. The
excess load can be connected to another power pack.

LED Indicator:

The LED indicates the following conditions on the BZ-50:
• LED OFF: no power to the BZ-50, or the +24VDC output is shorted.
• LED ON, blinks once every 5 seconds: the relay is closed (load ON).
• LED ON continuously: the relay is open (load OFF).
• LED blinking continuously: current output limit is exceeded (too many sensors are connected to the power pack); +24VDC output
shut down.
Optional
Local
Off
Switch
Red
Red
Control Output
Any
24VDC
Common
Ceiling/Wall
+24VDC
Sensor
Optional
Local
Off
Switch
Red
Red
Any
24VDC
Ceiling/Wall
Sensor with
an RJ45 Jack
White
Neutral
Line 120VAC
Black
277VAC
Fixture
Class 2
Low Voltage
Wires
*To
Additional
Sensor(s)
Neutral
White
Line 120VAC
Black
277VAC
Neutral
BZ-50RC with standard sensor, using FS-C2 cable
Neutral
White
Line
120VAC
Black
Fixture
277VAC
*To
Additional
Sensor(s)
with RJ45 jacks
(requires FS-C4
splitter)
OPERATION
2
BZ-50 Parallel interconnect for multiple
load control from a single sensor
Red
BZ-50
Red
Power Pack
Control Output
Common
+24VDC
Cap
Red
BZ-50
Red
Power Pack
Red
BZ-50RC
Red
Power Pack
FS-C2
cable
Control Output
(Yellow)
Common (Black)
+24VDC (Red)
Optional
Local
Off
Switch
Fixture
Any
*To
24VDC
Additional
Ceiling/Wall
Sensor(s)
Sensor
Optional
Local
Off
Switch
Fixture
Optional
Local
Off
Switch
Fixture
Any
24VDC
*To
Additional
Ceiling/Wall
Sensor(s)
Sensor