Leviton 1000 Serie Manual De Instalación página 10

Ocultar thumbs Ver también para 1000 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

2
TECHNICAL SPECIFICATIONS
Voltage Inputs
L3
L2
L1
N
CT Inputs (J1, Left Side)
CT3: X1
CT3: X2
CT2: X1
CT2: X2
CT1: X1
CT1: X2
CT Inputs (J1, Right Side)
10, Isolated Output (10 Wh/P, Kh = 10
COM, Isolated Output
1K, Isolated Output (1 kWh/P, Kh = 1000)
1 kWh LED (D3 – Green)
10 Wh LED (D2 – Green)
Reverse Phase LED (D1 – Red)
Description
Voltage Input Line 3
Voltage Input Line 2 (3-wire and 4-wire models only)
Voltage Input Line 1
Neutral Input (Meter powered from L1 & N)
Current Transformer input CT3 Colored wire of CT3
(4 wire models only)
Current Transformer input CT3. White wire of CT3
(4 wire models only)
Current Transformer input CT2. Colored wire of CT2
(3-wire and 4-wire models only)
Current Transformer input CT2. White wire of CT2
(3-wire and 4-wire models only)
Current Transformer input CT1. Black or colored wire
of CT2
Current Transformer input CT2. White wire of CT1
Isolated pulse output: 5 watt/hours on, 5 watt/hours
off, referenced to ISOL COM
Isolated common for 10/1000 isolated outputs
Isolated pulse output: 500 watt/hours on, 500 watt/
hours off, referenced to ISOL COM
50% duty cycle (at constant load) LED with a pulse
rate of 1 kWh per on/off cycle (500 watt/hours on,
500 watt/hours off). In the absence of a significant
load, the LED could be on, or off.
50% duty cycle (at constant load) LED with a pulse
rate of 10 Wh per on/off cycle (5 watt/hours on,
5 watt/hours off). In the absence of a significant load,
the LED could be on, or off.
Illuminates when a problem with meter phasing
exists. In the absence of a significant load, the LED
could be on or off. See section 3.7 for CT installation
instructions.
10

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

2000 serie

Tabla de contenido