Connect the UPS to the mains power supply using the input supply cable. Connect the loads to the UPS sockets
with the IEC-IEC cables or with a similar cable with a maximum length of 10 metres.
Note: do not connect loads that draw more than 10A, to the 10A IEC sockets. These loads can only be
connected to the 16A IEC socket (where fitted).
C
ONNECTION TO THE
A telephone/modem/network line can be connected to the modular RJ-45/RJ-11 connectors (located on the rear
of the UPS) to protect against surge voltages. A telephone extension cable is required for this type of
connection.
N.B.: This connection is optional. The Net/Tel protection is active even when the UPS is switched off or
disconnected from mains power.
Warning: The device that protects against overvoltages on the telephone line may not work if it is not installed
correctly. Ensure that the telephone line from the wall is inserted in the connector marked "IN" and that the cable
of the device to be protected (telephone, modem, network card, etc.) is inserted in the connector marked "OUT".
N.B.: This protection device limits the effects of an overvoltage but does not guarantee absolute protection.
P
OWERSHARE
All the models of the Dialog Vision range are provided with an auxiliary output socket that can be configured via
UPSTools. The Powershare socket can be configured in five different ways (refer to the UPSTools manual) as
described below:
 ALWAYS: (standard configuration), the Powershare socket is always active; the load is powered, as if it
were connected to one of the other output sockets.
 BATTERY LOW: the Powershare socket is normally active, but after 10 seconds from the start of the
battery low signal, the Powershare socket is deactivated.
 BATTERY WORKING: the Powershare socket is active if the UPS is powered from the mains power
supply, if the UPS is working in battery mode; the Powershare socket is deactivated.
 BATTERY WORKING DELAYED: the Powerashare socket is always active, but after 1 minute of
operation in battery mode or after 10 seconds in a battery low condition, the Powershare socket is
deactivated.
 BUZZER: when the UPS is working in battery mode, the Powershare socket is activated and deactivated
in the same way as the buzzer.