Load Wiring

Incandescent Load Types
Dimmed Hot/Live (DH/DL) must be used for non-dim loads
whether they will be dimmed or switched
Bypass
jumper
DH
SH H
Dimmable or non-dim load
TVM Load Types
Load terminals
Bypass jumper
L
DH
SH H
N
Neutral bus
Notes
• For 230 V
and 240 V
to as "Live". Therefore, terminals will be labeled DL,
SL, and L.
• Run wiring so that line (mains) voltage wiring will be at
least 6 feet (1.8 m) from sound or electronic
equipment and its wiring.
• Hot/Live (H/L) is used for bypass on all panels. It can
also be used as a protected Hot/Live output on GP3,
GP8, GP12, GP16, GP20, and GP24. (Added hot/live
current plus load current must not exceed breaker
limits.)
16 Installation Guide for Dimming Panels
Load terminals
Neutral bus
TVM
+
+ 1 –
Ballast
+ 2 –
panels, "Hot" is referred
Hi-Lume
FDB or Eco-10
®
fluorescent dimming ballasts
Eco-10 or
Hi-Lume FDB
ballast
Ballast
Fluorescent lamp
ELV Load Types
Dimmed Hot/Live (DH/DL) must be used for non-dim loads
whether they will be dimmed or switched
Load terminals
DH
SH H
Load
Caution! Verify with electronic low-voltage
transformer or ballast manufacturer that
product can be controlled with a phase
control or leading edge dimmer before bypass
jumpers are removed.
Caution! Switched Hot/Live (SH/SL) must be
used for only Hi-lume FDB or Eco-10 loads.
Use Dimmed Hot/Live (DH/DL) for all non-dim
loads.
Danger! Feed-through panels, such as GP4,
may be fed by multiple circuits. Locate and
lock each supply breaker in the OFF position
before wiring feed or loads.
Warning! CE-marked panels are appliances.
A distribution panel must provide a main
circuit breaker that does not exceed the
rating of the panel.
TM
Load terminals
Bypass
jumper
DH
SH H
Neutral bus
Bypass
jumper
Neutral bus
R