DIFUSOR LINEAL DE RETORNO / RETURN SLOT DIFFUSER
DATOS DE RENDIMIENTO / PERFORMANCE DATA
ANCHO
No. DE
A / PIE
K
DE
RANURAS /
AREA
RANURA /
Nº OF
A / FT.
K
SLOT SIZE
SLOTS
1
.03
2
.06
.08
3
1/2"
4
.11
5
.14
(12.7 mm.)
6
.16
7
.20
8
.22
No. DE
ANCHO
A / PIE
RANURAS /
DE
K
AREA
Nº OF
RANURA /
A / FT.
SLOT SIZE
SLOTS
1
.04
.08
2
.12
3
3/4"
4
.16
5
.20
(19.0 mm.)
6
.24
7
.28
.32
8
ANCHO
No. DE
A / PIE
K
RANURAS /
DE
AREA
Nº OF
RANURA /
A / FT.
K
SLOTS
SLOT SIZE
1
.06
2
.11
3
.17
1"
4
.23
5
.28
(25.4 mm.)
6
.33
7
.39
8
.44
NOTAS:
NC - LOS VALORES DE NC ESTAN BASADOS EN UNA ATENUACION DEL CUARTO
DE 10dB, Re 10-12 VATIOS, Y UN DIFUSOR DE 1.22 MTS. DE LONGITUD ACTIVA CON
DUCTO. PARA LNGITUDES DIFERENTES REFERIRSE A LOS DATOS DE INGENIERIA.
PS - PRESION ESTATICA NEGATIVA, EN PULGADAS DE AGUA, MEDIDA EN LA
ENTRADA DEL AIRE DE RETORNO.
Ak/PIE - AREA EFECTIVA, EN PIES CUADRADOS DE DIFUSOR ACTIVO POR PIE DE
LONGITUD.
PCM/PIE - EL VOLUMEN DE AIRE DE RETORNO POR PIE LINEAL DE DIFUSOR, EN
PIES CUBICOS POR MINUTO.
NAMM
grupo namm, s.a. de c.v
Marca registrada y modelo protegido por varias patentes y diseños industriales. Prohibido la reproducción parcial o total,
copia, comercializacion o cualquier actividad no autorizada de este modelo y/o contenido de la ficha técnica.
NC 20 - 25
SinDucto/Application non-ducted
- 0.02" PS
- 0.03" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
15
20
35
45
55
70
70
85
90
110
135
110
130
160
140
170
NC 20 - 25
Sin Ducto/Application non- ducted
- 0.02" PS
- 0.03" PS
K
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
25
35
50
60
80
100
100
120
130
160
160
195
175
215
200
245
NC 20 - 25
Sin Ducto/Application non- ducted
- 0.02" PS
- 0.03" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
35
43
70
85
105
130
140
170
175
215
255
210
245
300
280
340
mty,nl (81) 1292 4019
MODELO DLR
NC 30
Con Ducto/Application duc ted
- 0.08" PS
- 0.10" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
30
35
70
80
110
125
140
155
180
200
220
245
260
290
280
310
NC 30
Con Ducto / Application ducted
- 0.08" PS
- 0.10" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
50
65
100
110
160
180
200
225
260
295
320
360
350
390
400
445
NC 30
Con Duct o / App lication ducted
- 0.08" PS
- 0.10" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
70
80
140
155
210
235
280
310
350
390
420
465
490
545
560
620
NOTES:
NC - THE NC VALUES ARE BASED ON ROOM ATTENUATION OF 10 dB, Re 10-12 WATTS,
AND ONE DUCT CONNECTED 4 FOOT ACTIVE DIFFUSER LENGTH.
FOR LENGTH OTHER THAN 4 FOOT, REFER TO ENGINEERING DATA.
SP - NEGATIVE STATIC PRESSURE, INCHES OF WATER MEASURED IN RETURN INLET.
Ak/FT - EFECTIVE AREA, IN SQUARE FEET OF ACTIVE DIFFUSER PER FOOT OF LENGTH.
CFM/FT - THE VOLUME OF RETURN AIR PER LINEAL FOOT OF DIFFUSER IN CUBIC FEET
PER MINUTE.
.
cdmx (55) 5264 2606
NC 35 - 40
Con Ducto / Application ducted
- 0.15" PS
- 0.20" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
40
45
95
110
150
175
190
220
285
245
300
345
355
410
385
440
NC 35 - 40
Con Ducto / Application ducted
- 0.15" PS
- 0.20" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
75
90
135
160
220
250
320
275
420
360
440
510
475
550
630
545
NC 35 - 40
Con Ducto / Application ducted
- 0.15" PS
- 0.20" PS
PCM / PIE
PCM / PIE
CFM / FT.
CFM / FT.
95
110
190
220
285
330
440
380
550
475
570
660
665
770
880
760
.
www.namm.com.mx
A250620