4. Access to Maintenance and Personalization Data
Output Personalization
Function
Output voltage
(1)
Frequency converter
Output frequency
Transfer to the bypass
AC input
(1)
Overload level
(1)
ON/OFF Personalization
Function
Start on battery power Enabled
Automatic restart
Energy savings
Detection of phase/
neutral inversion
(SWF)

Battery Personalization

Function
Battery test
Selection of the
backup time
Battery protection
against excessive
discharges
4.4

Personalization Using External Software

Insert the Solution-Pac CD-ROM in the drive.
w
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
w
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
w
Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.
(1). These Parameters may be modified only when the UPS is OFF.
(2). Bypass is disabled when frequency converter is enabled.
86-86710-00EN A02 - Page 22
Factory Setting
120 Volts AC
Disabled
(1)
Automatic selection
(1)
Bypass AC power must be
within tolances
102%
Factory Setting
Enabled
Disabled
Enabled
Factory Setting
Weekly test
Automatic detection of
number of battery modules
Enabled
Options
100/104/110/120/127 Volts AC
Enabled
(2)
50 or 60 Hz
Bypass AC power may be
outside tolerances
50 / 70%
Options
Disabled
Disabled
Enabled
Disabled
Options
No test / daily test / monthly
test
0 to 200 Ah
Disabled
Comments
The connected devices are never
transferred to the bypass.
User selectable only if the
frequency-converter function is
enabled.
Alarm if threshold is overrun.
Comments
The UPS restarts automatically
when AC power returns.
When function enabled, battery
shuts down when power drops
to <5%.
When function enabled, the UPS
remains OFF if the system detects
phase/neutral inversion.
Comments
UPS restarts automatically when
Normal AC source is restored.
When function disabled, EATON
warranty no longer applies.