OPERATING INSTRUCTIONS
FOR INSULATING POLES
ENGLISH
STORAGE INSTRUCTIONS
Insulating poles should be stored in their packaging or sleeve, and placed so they
will not become deformed.
Avoid storing them near sources of light or heat (e.g. heating pipes, radiators,
etc.).
Store between temperatures of -10 °C and +35 °C
TRANSPORT INSTRUCTIONS
When transporting insulating poles they should be carried in transport cases to
minimise wear and tear.
During transport, ensure poles cannot be bumped or scraped against other
materials, and avoid placing heavy objects on top.
INSTRUCTIONS FOR USE
Check before operating:
Before use, each pole should be visually inspected by the user.
If there is any doubt about the pole's safety, it should be rejected or checked by
an expert and if necessary subjected to testing.
It is not advised to carry out work involving electrical hazards during times of
rainfall, and in wet conditions it is advisable to use BSC MODEL references.
It is advised to take additional preventive measures, such as wearing a safety
helmet and electrical safety gloves when carrying out work involving electrical
hazards.
For poles made with different sections, these can be changed out for others (of
the same model), provided the sections can be properly identified.
Precautions during use:
Poles should not be exposed unnecessarily to light or heat, and contact with
chemical substances that could affect them (oil, grease, solvents, etc.) should
be avoided. Poles used in rainfall or high levels of condensation should be siliconed
first.
After use the pole should be cleaned, and if possible siliconed.
MAINTENANCE INSTRUCTIONS
Poles should be kept clean. If necessary, it is recommended to clean the pole
with silicone.
Users should devise a maintenance programme for poles to ensure they are
kept in good condition.
As manufacturer of insulating poles, SOFAMEL S.L. advises conducting regular
electrical checks every 6 years.
WARRANY: Subject to proper use of the detector, our warranty extends for 24 months from sale. If you need any assistance, please contact our technical services or your SOFAMEL nearest distributor: Tel.: +34 938087980
FEATURES AND USE
Operators should choose the appropriate model of insulating pole depending on the requirements of the task and the level of insulation needed. The minimum lengths of
the pole's insulating elements should be taken into account, in accordance with the provisions of Royal Decree 614/2001 of 8 June on minimum provisions for protecting
the health and safety of workers from electrical risks.
"D" LIMIT DISTANCES OF WORK ZONES AT AN UNPROTECTED VOLTAGE POINT
Un
Nominal Voltage
Working with Live Voltage
in thousands of Volts
ONLY QUALIFIED PERSONNEL
< 1 kV
3 kV
6 kV
10 kV
15 kV
20 kV
30 kV
45 kV
66 kV
110 kV
132 kV
220 kV
380 kV
Un
Nominal Voltage of the installation in kV.
Dpel-1
Distance to the outer limit of the danger zone when there is a risk of lightning surge (cm).
Dpel-2
Distance to the outer limit of the danger zone when there is no risk of lightning surge (cm).
Dprox-1
Distance to the outer limit of the proximity zone when it is possible to accurately delimit the work area and control that this is not breached during
performance of the work (cm).
Dprox-2
Distance to the outer limit of the proximity zone when it is not possible to accurately delimit the work area and control that this is not breached during
performance of the work (cm).
WORKS CLOSE TO THE BARE CONDUCTORS
Live
Dprox-1
When IT IS possible to accurately
Element
determine the work area.
Dpel-1
Dprox-2
When IT IS NOT possible to accurately
determine the work area.
D
cm
It is mandatory to heed
Dprox-1 or Dprox-2
Based on the specific case scenario shown in the above table and depending on:
Qualification of personnel and delimitation of the work area.
Dpel-1
Dpel-2
Danger Distance
of works close by
50 cm
50 cm
62 cm
52 cm
62 cm
53 cm
65 cm
55 cm
66 cm
57 cm
72 cm
60 cm
82 cm
66 cm
98 cm
73 cm
120 cm
85 cm
160 cm
100 cm
180 cm
110 cm
260 cm
160 cm
390 cm
250 cm
Dprox-1
Dprox-2
70 cm
300 cm
112 cm
300 cm
112 cm
300 cm
115 cm
300 cm
116 cm
300 cm
122 cm
300 cm
132 cm
300 cm
148 cm
300 cm
170 cm
300 cm
210 cm
500 cm
330 cm
500 cm
410 cm
500 cm
540 cm
700 cm
WORKS CLOSE TO CONDUCTORS WITH A
PHYSICAL BARRIER IN PLACE
Physical barrier
DOES NOT CONDUCT ELECTRICITY
Dprox-1
When IT IS possible to accurately
determine the work area.
Dpel-1
Dprox-2
When IT IS NOT possible
to accurately determine
the work area.
D
cm
It is mandatory to
heed Dprox-2