Digital input polarity 2
P13
0=Energised on closed contact, 1=Energised on open contact
Maximum start-up time after pump down
P14
(Values between 1 and 9 seconds are not accepted) (0=Disabled)
P15 Maximum pump down time (0=Disabled)
P22 Cold room light timer
P23 Stop fans and compressor on opening door
P24 Start up delay for fans and compressor with door open
EP Exit Level 1
Level 1.- Access control and information (tid)
L5 Access code (Password)
PU Program version (Information)
Pr Program revision (Information)
EP Exit Level 1
10.- Technical specifications
Power supply
AKO-15645 / AKO-15646 / AKO-15626 / AKO-15627
AKO-15648 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400 V~ ±10 % 50 Hz ±5 %
Total maximum current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 A (Page 23, 24)
COMPRESSOR relay (20 A)
AUX 1 relay (16 A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (2) A to 230V~ SPST
AUX 2 relay (8 A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (2) A to 230V~ SPDT
FAN relay (16 A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 (3) A to 230V~ SPST
DEFROST relay (16 A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 A to 230V~ SPST
Probe temperature range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50.0 ºC to 99.9 ºC
Resolution, setting and differential . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.1 ºC
Thermometric precision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 ºC
Tolerance of the NT
C probe at 25 ºC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0.4 ºC
Input for NTC probe. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-14901
Maximum input power in the operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 VA
Working ambient temperature of the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -5 ºC to 40 ºC
Working ambient temperature of the button AKO-520622 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -20 ºC to 70 ºC
Storage ambient temperature of the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 60 ºC
Storage ambient temperature of the button AKO-520622 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -20 ºC to 70 ºC
Overvoltage category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II s/ EN 61439-1
Pollution degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II s/ EN 61439-1
Protection degree of the panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP65 (Page 17)
Protection degree of the button AKO-520622 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 65
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230(An) x 230(Al) x 95(P) mm
Double isolation between power supply, secondary circuit and relay output.
Type of assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Internal buzzer
Encapsulated assembly
Description
0=No
Description
AKO-15645 / AKO-15646 / AKO-15626 / AKO-15627
AKO-15648 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 (9) A to 230V~ SPDT
1=Si
. . . . . . . . . . . . . . . 230 V~ ±10 % 50 Hz ±5 %
30
Units
Min
Def
Max.
0
0
(seg.)
0
0
120
(min.)
0
0
15
(min.)
0
0
999
0
0
(min.)
0
0
999
Units
Min
Def
Max.
0
0
99
-
-
. . . . . 11 (11) A to 230V~ SPDT
Fixed internal
1
1