To enable floor protection, set the following codes:
1st
2nd
code
code
(a) Can be modified as preferred.
(b) Default value. Can be modified as preferred.
To enable dew prevention, set the following codes:
The dew prevention function can only be enabled if
NOTE
floor temperature protection is enabled (refer to the
table above).
1st
2nd
code
code
Should condensation on the floor occur, we suggest
increasing field settings
conditions are so extreme that this countermeasure
is not adequate, we suggest not to use floor cooling.
RKRTR + EKRTETS
Room thermostat
4PW56107-1
Description
External temperature
sensor EKRTETS
installed?
Enable floor high/low
temperature limit?
Lower limit of floor
temperature
Upper limit of floor
temperature
Description
Enable dew prevention
function?
Offset for dew point
calculation
Display result of dew
point calculation
Required
setting
ÌlË
ÌlË
(a)
(a)
(b)
(b)
Required
setting
ÌlË
Consult
only
and
. In case the
Installation manual
Step
—
—
0.5°C
0.5°F
0.5°C
0.5°F
Step
—
0.1°C
0.2°F
—
16