Remote Annunciator
7
Address Setting
Each FMR-1000-RA connected to the Option Bus of the FPA-1000 must be set to a unique
Option Bus address ranging from 16 to 23. The devices must also be programmed at the
control panel (refer to FPA-1000 Installation and Operation Guide (P/N F.01U.173.607).
The address is set using the DIP switches at the main board of the annunciator unit. Refer to
Table 7.1.
Figure 7.1 Address Setting
Table 7.1 DIP Switch Function
NOTICE!
Each Option Bus device must have its own address, and each address can support only one
device. Ensure that there are no duplicate addresses on the bus.
8
Programming
All Remote Annunciators and Remote Command Centers have to be configured as elements
connected to the Option Bus.
The FPA-1000 enables various programming approaches:
–
–
–
–
For front panel programming, the system provides an auto learn function, allowing the
installer to configurate the system quickly and easily in default mode.
Bosch Security Systems, Inc.
ON
DIP
ON
OFF
1
2
3
4
5
Option Bus
DIP 1
Address
16
OFF
17
ON
18
OFF
19
ON
20
OFF
21
ON
22
OFF
23
ON
On-site at the front panel to program another panel, but not all parameters can be
programmed
On-site through a Web server using a laptop (connected to the panel with CAT5 cable)
Remote, using a Web page and a dial-up connection
Remote, using a Web page and an Ethernet connection.
Installation and Operation Guide
ON
ON
1
2
3
OFF
ON
ON
ON
DIP
1
2
3
4
5
1
2
3
OFF
ON
ON
1
2
3
OFF
ON
ON
1
2
3
OFF
DIP 2
DIP 3
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
Address Setting | en
16
ON
DIP
ON
DIP
4
5
1
2
3
4
5
OFF
17
ON
DIP
ON
DIP
4
5
1
2
3
4
5
OFF
18
ON
DIP
ON
DIP
4
5
1
2
3
4
5
OFF
19
ON
DIP
ON
DIP
4
5
1
2
3
4
5
OFF
DIP 4/DIP 5
For the FMR-1000-RA,
DIP 4 and 5 must be at
OFF position.
F.01U.078.097 | 3.0 | 2011.11
11
20
21
22
23