4 CONFIGURATION
Modbus Address: Before the A8911-23 can be used, you must set the Modbus
address of the A8911-23. This address must be unique among all Modbus
devices in the system. The A8911-23 supports address 1 through 127.
Select an address and set the DIP switches to match.
The sum of the value of the switches is the address. In the example to the right,
address 52 is set by placing switch 4, 16 and 32 to the on position.
Note: 4 + 16 + 32 = 52
Baud Rate: This option sets the serial port speed for the RS485 port. Set this
option to [OFF] for 19200. Set the switch to [ON] for 9600 baud.
5
on
1
2
4
8
16
32
64
19200/9600