AERMEC WMT21 Manual De Instrucciones página 131

Termostato a display per fan coilcon uscita ventilatore 0-10v
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Room temperature
0
0
P12
.
offset (°F)
Heating set-point
50
P13
lower limit (°F)
Heating set-point
86
P14
upper limit (°F)
Cooling set-point
P15
50
lower limit (°F)
Cooling set-point
P16
86
upper limit (°F)
Anti-freeze threshold
P17
32
temperature (°F)
Economy
P18
0
reduction (°F)
Room temperature
P19
0
4
.
hysteresis (°F)
Neutral zone
P20
5
0
.
width (°F)
Fan delay at
0
P21
turn-on (seconds)
Fan delay at
0
P22
turn-off (seconds)
Heating delivery
104 P23
temperature threshold (°F)
12
0
12
0
59 P24
-
..
.
.
41 
  95   
0
. .
41 
  95     
. .
41 
  95 
. .
41 
  95 
. .
32 
  60
. .
0 
18
. .
0
4 
1
8
. .
.
.
0
0 
20
0
. .
.
.
FAHRENHEIT DEGREES TEMPERATURE SETTING
In order to set the measurement unit from Celsius degrees to Fahrenheit
0 
  600
. .
degrees and vice versa, enter the configuration mode by holding down the
keys " " and "" until the display shows "Con", then hold down the
0 
  600
. .
two keys " " and "" for a few seconds, until the display returns to
the usual screen.
32 
  210
Switching from Celsius to Fahrenheit or vice versa also forces a reset of
. .
the installer configuration to default values.
131
Cooling delivery
temperature threshold (°F)
Dirty filter warning
P25
time (x 100 hours)
32 
  210
. .
0 
  50
. .