The connection to a Building Management System (BIS) is done via an OPC server and the
Ethernet 100BaseTX interface. For a multiple-building network, you must check with the
network adminstrator if
Address Setting and Configuration
1.
2.
3.
Note the DIP switch and address settings for the stand-alone and redundant configuration
(Figure 9, Page 10).
NOTICE!
DIP 6 on the Panel Controller of the FPA-1200 is inoperable, as it cannot be operated as a
redundant panel.
Technical Specifications
LCD display / touch screen
Operating and display elements
Interfaces
Signal inputs
Max. CAN cable length in networks
Input voltage
Power supply PRS 0002 A
Max. current consumption
Permissible operating temperature
Permissible storage temperature
Dimensions (H x W x D)
Weight
F.01U.258.925 | 2.0 | 2012.04
the network is designed for multiple-building connections (e.g. no technical interference
by varying ground potentials)
the bus users are designed for the network
Assign a unique physical address to each Panel Controller and Remote Keypad by setting
the rotary switches and write it down on the label (Step 1 and 2, Figure 7, Page 9).
Make sure that the redundant panels do have identical addresses.
For configuration, set the 6-pin DIP switch (Step 3, Figure 7, Page 9).
Mark the setting on the provided label (Step 4).
320 x 240 pixels / 127.5 mm x 170 mm active surface
22 keys, 1 key switch, 11 LEDs, 1 reboot button
CAN1, CAN2, ETH1, ETH2, USB, RS232
IN1/IN2
L
= 1000 m, depending on configuration, cable type and topology
max
20 V DC to 30 V DC
+5 V DC ±4.5 % / max. 500 mA
-
Standby: 135 mA at 24 V DC
-
During alarm: 225 mA at 24 V DC
-5 °C to +50 °C
-20 °C to +70 °C
190 mm x 404 mm x 60 mm
Approx. 2 kg
MPC-xxxx-C / FPA-1200-MPC-C