Puesta en marcha
5.3.2 Asistente de arranque para aplicaciones de lazo cerrado
1-25 Motor nominal speed
5
5
6-22 T54 Low Current
04.66
Setup 1
6-24 T54 low Feedback
0016
Setup 1
6-23 T54 high Current
13.30
Setup 1
6-25 T54 high Feedback
0050
Setup 1
Ilustración 5.7 Asistente de configuración de lazo cerrado
30
PM motor
1-24 Motor Current
A
3.8
Setup 1
3000
RPM
Setup 1
1-26 Motor Cont. Rated Torque
5.4
Nm
Setup 1
1-30 Stator resistance
0.65
Ohms
Setup 1
1-39 Motor poles
8
Setup 1
1-40 Back EMF at 1000 rpm
57
V
Setup 1
1-37 d-axis inductance(Ld)
5
mH
Setup 1
4-19 Max Ouput Frequency
0065
Hz
Setup 1
Current
A
Hz
A
Hz
Danfoss A/S © Rev. 06/2014 Reservados todos los derechos.
Manual de funcionamiento
0-03 Regional Settings
[0]
International
Setup 1
0-06 Grid Type
[12]
380-440V/50Hz
Setup 1
1-00 Con guration Mode
[3]
Closed Loop
Setup 1
1-10 Motor Type
[0]
Asynchronous
Setup 1
4-12 Motor speed low limit
0016
Hz
Setup 1
4-14 Motor speed high limit
0050
Hz
Setup 1
3-41 Ramp 1 ramp-up time
0003
s
Setup 1
3-42 Ramp1 ramp-down time
0003
s
Setup 1
MotorType = PM Motor
20-00 Feedback1 source
[1]
Analog input 54
Setup 1
3-02 Min Reference
0.00
Setup 1
3-03 Max Reference
50.00
Setup 1
3-10 Preset reference [0]
0.00
%
Setup 1
6-29 Terminal 54 Mode
[1]
Voltage
Setup 1
6-26 T54 Filter time const.
0.01
s
Setup 1
20-81 PI Normal/Inverse Control
[0]
Normal
Setup 1
20-83 PI Normal/Inverse Control
0050
Hz
Setup 1
20-93 PI Proportional Gain
00.50
Setup 1
20-94 PI integral time
0020.00
s
Setup 1
1-29 Automatic Motor Adaption
[0]
O
Setup 1
Asynchronous Motor
1-20 Motor Power
1.10
kW
Setup 1
1-22 Motor Voltage
0050
V
Setup 1
1-23 Motor frequency
0050
Hz
Setup 1
1-24 Motor current
04.66
A
Setup 1
1-25 Motor nominal speed
1420
RPM
Setup 1
MotorType = Asynchronous
1-73 Flying Start
[0]
No
Setup 1
Resource
This dialog is forced to be set to
[1] Analog input 54
Voltage
6-20 T54 low Voltage
0050
V
Setup 1
6-24 T54 low Feedback
0016
Hz
Setup 1
6-21 T54 high Voltage
V
0220
Setup 1
6-25 T54 high Feedback
0050
Hz
Setup 1
MG03L205