Table 3: C10 parameter - Fan speed " " button limitation.
VALUE
0
1 2 3 AUTO
1
1 2 AUTO
2
1 AUTO
3
OFF 1 2 3 AUTO
4
OFF 1 2 AUTO
5
OFF 1 AUTO
6
OFF 1
7
OFF
8
1
9
2
10
3
11
AUTO
12
1 2 3
13
1 2
14
OFF 1 2 3
15
OFF 1 2
DESCRIPTION
Table 4: PARAMETERS C17, C18, C19 -
Function associated to 3, 4 and 16 inputs.
VALUE
0
No function associated.
"Centralised Summer/Winter" function (closed contact =
1
summer); P02 parameter configured to 2.
"Reversed centralised Summer/Winter" function (closed
2
contact = winter); P02 parameter configured to 2.
3
"Economy" function (closed contact = reduction).
"Economy" function (closed contact = reduction) - display
4
shows the "
5
"Reversed economy" function (contact open = reduction).
"Reversed economy" function (contact open = reduction)
6
- display shows the "
7
"Stop adjustment" function (closed contact = stop adjustment).
"Stop adjustment" function (closed contact = stop
8
adjustment) - display shows the "
(absent) icon.
"Stop adjustment" function (closed contact = stop
9
adjustment) - display shows the "
"Stop adjustment" function (closed contact = stop
10
adjustment) - display shows the "
60
DESCRIPTION
" (present) or "
" (absent) icon.
" (present) or "
" (absent) icon.
" (present) or "
" icon.
" icon.
LXTFZ01M-IOM-1502
"