Troubleshooting - Marlec Rutland 504 E-Furl Manual Del Usuario

Tabla de contenido

Publicidad

Rutland 504 "e-Furl" Windcharger
Trouble Shooting
In the unlikely event that your Rutland 504 "E-Furl" should develop a defect, the turbine
should first be tied to prevent the blades from turning to perform the static tests below.
(Follow the procedure described in the Inspection and Maintenance section). It will be
necessary to let it run for the tests to check for power production.
1
. Read the 12 Steps Quick Start Guide and Up and Running sections and be
satisfied that your system complies.
2. Is there sufficient wind? The Rutland 504 "E-Furl" needs 5 knots wind speed to start
charging. The wind speed across the turbine blades may be greatly reduced in
a marina or built-up area compared with the reading on a masthead anemometer
or weather reports.
3. Static Tests:
Is the battery in good condition?
each battery.
Check electrical continuity throughout the system, especially corrosion
and poor connections in cable joins and connector blocks.
4. Running Tests:
Check for power output from the windcharger following this procedure:
A Set a digital multi-meter to DC Amps, scale of up to 5A or less if possible. Connect the
meter positive (+) probe to the wind gen output positive cable and the meter negative
(-) to the regulator input positive. Provided there is sufficient wind there should be a
current reading. This establishes that power is being delivered.
B Using the same multi-meter setting as above measure between the "regulator to
battery" + and the battery +. Provided there is sufficient wind there should be a
current reading. This establishes if power is passing through the regulator.
C If both above are unsuccessful set the multi-meter to DC Volts. Disconnect the wind
generator from the regulator and connect the meter + to the wind gen + and the meter –
to the wind gen -. Provided there is sufficient wind there should be a variable voltage
reading according to the speed of the wind seen at the wind turbine. This will establish if
the wind generator is able to deliver power or not.
D If tests A and C are successful but test B fails to produce results connect the wind gen
directly to the battery. Set the digital multi-meter to DC Amps and measure power
between the wind gen + and the battery +. If a reading is measured, providing there is
sufficient wind, then the regulator is faulty.
E If the wind turbine fails to deliver any current or open circuit V reading undertake the
further tests below.
Doc. No: SM-151 Issue A 07/01/2011
Check the voltage and electrolyte level of
17
Installation and Operation
Marlec Engineering Co

Publicidad

Tabla de contenido
loading

Tabla de contenido