Electrical Ratings - Emerson White-Rodgers 50E47-843 Instrucciones De Instalación

Ocultar thumbs Ver también para White-Rodgers 50E47-843:

Publicidad

Idiomas disponibles

Idiomas disponibles

SPECIFICATIONS

ELECTRICAL RATINGS:

Input Voltage: 18 to 30 VAC, 60 Hz
Current: 0.2 amp
Relay Contact Ratings:
Valve Relay:
1.5 amp @ 25 VAC 60 Hz 0.6 PF
Ignitor Relay:
6.0 amp @ 120 VAC 60 Hz-
resistive
Flame Current Requirements:
Minimum current to insure flame detection: 2 µA DC*
Maximum current for non-detection: 0.2 µA DC*
Maximum allowable leakage resistance: 100 M ohms
* Measured with a DC microammeter in series with the flame
probe lead
OPERATING TEMPERATURE RANGE:
-40° to 175°F (-40° to 80°C)
HUMIDITY RANGE:
To 95% relative humidity (non-condensing)
MOUNTING:
Surface mount or 4" x 4" junction box
GASES APPROVED: Natural, Manufactured, Mixed, Liquid
Petroleum, and LP Gas Air Mixtures.
INSTALLATION
MOUNTING AND WIRING
WARNING
!
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
CAUTION
!
To prevent electrical shock and/or equipment dam-
age, disconnect electric power to system at main fuse
or circuit breaker box until installation is complete.
Failure to earth ground the appliance or reversing the
neutral and hot wire connection to the line can cause
shock hazard.
Shut off main gas to heating system until installation
is complete.
Route and secure all wiring as far from flame as practical
to prevent fire and/or equipment damage.
2
Program Key Timing Specifications Quick Reference
Timing and Retry
Program
Trial for
Key (Color)
Ignition
Retries
A (blue)
4 Sec.
B (red)
4 Sec.
C (green)
7 Sec.
D (violet)
7 Sec.
E (orange)
4 Sec.
F (yellow)
7 Sec.
NOTE: Program keys are lettered and color coded.
NOTE
Replace control as unit –no user serviceable parts.
All wiring should be installed according to local and national
electrical codes and ordinances.
The control may be mounted in any orientation on a
convenient surface using two #6 x 5/8" sheet metal screws.
If desired, control can be mounted on a 4" x 4" junction
box using two #8-32 x 5/8" machine screws. The control
must be secured to an area that will experience a minimum
of vibration and remain below the maximum ambient
temperature rating of 175°F. The control is approved for
minimum ambient temperatures of -40°F.
Refer to the wiring diagrams and wiring table when
connecting the control to other components of the system.
UL approved 105°C rated 18 gauge minimum wire is
recommended for all low voltage connections. UL approved
105°C rated 16 gauge minimum wire is recommended
for all line voltage connections. Refer to table below for
recommended terminals to mate with those on the control.
After installation or replacement, follow appliance
manufacturer's recommended installation/service instructions
to insure proper operation.
Interpurge
Ignitor
Prepurge
(Warmup)
0
30 Sec.
45 Sec.
2
30 Sec.
45 Sec.
0
30 Sec.
45 Sec.
2
30 Sec.
45 Sec.
2
30 Sec.
17 Sec.
2
30 Sec.
17 Sec.