Functioning And Setting Of The Installation; Initial Delay; Run-Out Period; Ordering Spare Parts - PLYMOVENT CB-WCS Instrucciones Pare El Uso

Caja de conexiones eléctricas
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 15
After connecting the mains, the extraction
fan, the WL and/or the AST and (if present)
the stationary self-cleaning welding fume
extractor (SFS)
[Statiflex
of the control box can be fitted again using
the mounting screws.
5.4

Functioning and setting of the installation

The CB-WCS has been exclusively designed to switch
the fan motor (FAN 14/28/42)
on and off, in combination with the automatic start/
stop device WCS. The fan's initial delay and the run-
out period can be adjusted to the user's wish.
The timer PC board (fig. 7) consists of the following
components:
A potmeter 1
B potmeter 2
C status leds
D fuse 2A
E connection WCS, AST, Filter
F connection 24 VAC
G relay contact

5.4.5 Initial delay

The initial delay can be set from 0 to 5 seconds via
potmeter 1 (fig. 7A). The initial delay is standard set at
0 seconds, so the fan will start immediatelly when
welding starts.

5.4.6 Run-out period

The run-out period can be set from 0 to 300 seconds
via potmeter 2 (fig. 7B). In most cases a run-out period
of 20 seconds will be sufficient. The run-out period is
standard set at 0 seconds.
When setting the installation, the functioning of the
timer PC board can be checked by the status leds
Power, Input and Output (fig. 7C) on the timer PC
board.
6
TROUBLESHOOTING
For remedying errors which apply to not
(correctly) functioning of the WL+AST and/
or the extraction fan (FAN 14/28/42)
1400/2400/4200], see the corresponding
manuals. If you cannot remedy any other
problems, contact your supplier.
7

ORDERING SPARE PARTS

The spare parts available for the product are given in
fig. 6.
Address your order to your supplier and always
state the data below:
- product name, supply voltage and serial number
0507346050/CB-WCS/010111/C
400-MS]. the cover
[SF 1400/2400/4200]
[SF
(see the identification plate)
- article number of the particular part (see the
electric diagram)
or:
- position number of the particular part (see fig. 6)
- description
- quantity
Pos. Article no.
Description
0326730020
Timer PC board
2
9870080160
Fuse 2,0 A (10 pieces)
4
0334100200
Transformer 50W/24V 115/
230/400V
5
0328410110
Relay LS 5.10
6
(NTR)
EC DECLARATION
EC declaration of conformity for machinery
We, Plymovent, Wezelkoog 11, 1822 BL Alkmaar, the
Netherlands, herewith declare, on our own
responsibility, that the products:
- CB-WCS
are in compliance with the Directives:
- 2006/95/EC
- 2004/108/EC
Alkmaar, the Netherlands, January 1, 2011
C.J.M. Knijn
Chief Operations Officer
EN - 7

Publicidad

Tabla de contenido
loading

Productos relacionados para PLYMOVENT CB-WCS

Tabla de contenido