Table 20 RTC113 ST-module, LXV412.99.00111, 2-channels (continued)
Module
Name
2-fold analog output KL4012
1-fold analog input
KL3011
1-fold analog input
KL3011
1-fold analog input
KL3011
1-fold analog input
KL3011
Bus end terminal
KL9010
Startup
User interface and navigation
Keypad description
Refer to
Figure 3
for the keypad description and navigation information.
Figure 3 Keypad description
1 Enter: Saves the setting and exits the current
screen to the CONFIGURE menu
2 Cancel: Exits the current screen to the
CONFIGURE menu without saving the setting
3 Add: Adds a new sensor to the selection
Add a sensor
Note: Make sure that an RTC communication card is installed in the sc1000 sensor module.
1. Connect the controller. Refer to the controller documentation.
2. Select MAIN MENU>RTC MODULES/PROGNOSYS>RTC
MODULES>RTC>CONFIGURE>SELECT SENSOR.
3. Push Add. Refer to
A list with all network connections shows.
4. Select the applicable sensor for the RTC module and push Enter. The sensor is shown in the
sensor list.
Note: The sensor names in black are available for an RTC module. The sensor names in red are not available
for an RTC module. A sensor name identified with a "(p)" is available for PROGNOSYS.
Terminal Signal
1(+) 3(-)
0/4 to 20 mA
5(+) 7(-)
0/4 to 20 mA
1(+) 2(-)
0/4 to 20 mA
1(+) 2(-)
0/4 to 20 mA
1(+) 2(-)
0/4 to 20 mA
1(+) 2(-)
0/4 to 20 mA
—
Figure
4.
Channel Function
2
Set point of the polymer flow rate
2
Set point of the feed flow rate
1
Input of the feed flow rate
1
Input of the polymer flow rate
2
Input of the feed flow rate
2
Input of the polymer flow rate
—
—
Bus termination
4 Delete: Removes a sensor from the selection
5 UP and DOWN arrows: Moves the sensors up or
down the list
English 19