RectorSeal AquaGuard AG-1100+ Instrucciones De Instalación

Interruptor de flotador magnético

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Wiring the AquaGuard
WORK SAFE, READ THIS!
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO
STARTING INSTALLATION MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
ATTENTION:
Clean surface with alcohol pad before mounting with adhesive tape.
Work Safe, READ THIS!
ATTENTION:
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
STOP/READ: This device must be installed in accordance with manufacturer's instructions. This unit must be in accordance with all applicable local plumbing, drainage and electrical
codes.
WARNING: Remove electrical shock hazard – DISCONNECT THE POWER BEFORE INSTALLING AQUAGUARD to avoid electrical shock and/or equipment damage.
Do not use on circuits exceeding 24 volts to avoid damage to switch, shock or fire hazard.
Work Safe, READ THIS!
CAUTION: In some situations the switch may cause the unit to rapidly cycle on and off as water level rises slowly in pan. After a brief period the unit will turn off completely.
Condensation drain must be serviced if this occurs.
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY
CAUTION: In any installation where property damage and/or personal injury might result from an inoperative switch due to power outages, a back-up system(s) and or alarm should be
CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
installed.
STOP/READ: This device must be installed in accordance with manufacturer's instructions. This unit must be in accordance with all applicable local plumbing, drainage and
NOTICE: The AquaGuard AG-1100+ must only be installed by a licensed contractor or under the direct supervision of same. Condensation pan must be properly maintained after
electrical codes.
installation and be kept free from foreign objects, rust or other obstructions that might interfere with the proper operation of the AquaGuard float switch.
WARNING: Remove electrical shock hazard – DISCONNECT THE POWER BEFORE INSTALLING AQUAGUARD to avoid electrical shock and/or equipment damage.
Do not use on circuits exceeding 24 volts to avoid damage to switch, shock or fire hazard.
INSTALLATION OF FLOAT SWITCH ON DRAIN PAN:
CAUTION: In some situations the switch may cause the unit to rapidly cycle on and off as water level rises slowly in pan. After a brief period the unit will turn off completely.
(To ensure proper performance of product, instructions must be followed.)
Condensation drain must be serviced if thisoccurs.
1. Disconnect power to unit at main panel. Disconnect power to the low voltage thermostat circuit.
CAUTION: In any installation where property damage and/or personal injury might result from an inoperative switch due to power outages, a back-up system(s) and or alarm
2. Slide the float switch onto the side of the pan.
should be installed.
3. Secure switch wires so they will not affect the operation of the float.
NOTICE: The AquaGuard AG-1100+ must only be installed by a licensed contractor or under the direct supervision of same. Condensation pan must be properly maintained
4. Secure the float switch by tightening thumb screws. (fig.1) Do not over tighten.
after installation and be kept free from foreign objects, rust or other obstructions that might interfere with the proper operation of the AquaGuard float switch.
WIRING THE AG-1100+ in a Conventional HVAC System:
INSTALLATION OF FLOAT SWITCH ON DRAIN PAN:
1. Ensure the power is disconnected to the unit at the main panel prior to moving to step 2.
(To ensure proper performance of product, instructions must be followed.)
Refer to the appliance manufacturer's installation and operating instructions and also review wire layout in their instructions.
2. Locate the red wire coming from the 24 volt thermostat "R" terminal.
1.
Disconnect power to unit at main panel.Disconnect power to the low voltage thermostatic circuit.
3. Disconnect or cut red wire. Connect the non-ribbed wire of the switch, using a wire nut, to the thermostat side of the circuit. Connect the ribbed wire of the switch, using a wire nut, to the
2.
Slide the float switch onto the side of thepan.
air handler side of the circuit or to terminal in unit. Incorporating both switch wires in the red circuit will shut the unit completely off.
5. Place the ATTENTION sticker on unit in a clearly visible location. (fig. 3)
3.
Secure switch wires so they will not affect the operation of the float.
4. Test the switch. (At start-up check initial amperage load.)
4.
Secure the float switch by tightening thumb screws. (fig.1) Do not over tighten.
A. With unit on, test switch by pulling the float pin up. (fig. 2) Unit should stop running if switch is correctly wired.
5. Place the ATTENTION sticker on unit in a clearly visible location. (fig. 3)
B. To test switch responsiveness fill pan with water to ensure that the switch stops the unit before the pan overflows. Remove water.
5. Place the ATTENTION sticker on unit in a clearly visible location. (fig. 3)
5. Place the ATTENTION sticker on unit in a clearly visible location. (fig. 3)
5. Place the ATTENTION sticker on unit in a clearly visible location. (fig. 3)
(fig.1)
(fig. 2)
WIRING THE AG-1100+ in a Conventional HVAC System:
(fig. 2)
(To ensure proper performance of product, instructions must be followed.)
(fig. 2)
1.
Ensure the power is disconnected to the unit at the main panel prior to moving to step 2.
(fig. 2)
Refer to the appliance manufacturer's installation and operating instructions and also review wire layout in their instructions.
6.
For wiring the normally open third wire (short wire) refer to the following diagrams:
2.
Locate the red wire coming from the 24 volt thermostat "R" terminal.
6. For wiring the normally open third wire (short wire) refer to the following diagrams:
3.
Disconnect or cut red wire. Connect the non-ribbed wire of the switch, using a wire nut, to the thermostat side of the circuit. Connect the ribbed wire of the switch,
using a wire nut, to the air handler side of the circuit or to terminal in unit. Incorporating both switch wires in the red circuit will shut the unit completely off.
Standard HVAC Installation
4.
Test the switch. (At start-up check initial amperage load.)
6.
For wiring the normally open third wire (short wire) refer to the following diagrams:
A. With unit on, test switch by pulling the float pin up. (fig. 2) Unit should stop running if switch is correctly wired.
B. To test switch responsiveness fill pan with water to ensure that the switch stops the unit before the pan overflows. Remove water.
Standard HVAC Installation
6.
For wiring the normally open third wire (short wire) refer to the following diagrams:
6.
For wiring the normally open third wire (short wire) refer to the following diagrams:
Standard HVAC Installation
Standard HVAC Installation
WIRING the AG1100+ in a Communicating HVAC System:
1. See equipment manufacturers recommendations for specific wiring instructions.
LIMITED WARRANTIES AND LIMITATION OF LIABILITY
REGISTER YOUR PRODUCT ONLINE: www.rectorseal.com
1 YEAR SWITCH AND SENSOR LIMITED WARRANTY AND LIMITATION OF LIABILITY
The limitations of liability set forth below include body and all component parts as well as the product itself as a whole.
RectorSeal warrants to the original consumer purchaser ("Purchaser) of its AquaGuard switch and sensor products, that they are free from defects in material or workman-
WIRING the AG1100+ in a Communicating HVAC System:
ship for a period of one (1) year from the date of purchase. If this product shall prove to be defective within the one (1) year period from the date of purchase, it shall be
WIRING the AG-1200+ in a Communicating HVAC System:
repaired or replaced, at RectorSeal 's option, subject to the GENERAL TERMS and CONDITIONS set forth below.
1.
See equipment manufacturers recommendations for specific wiring instructions.
1.
See equipment manufacturers recommendations for specific wiring instructions.
WIRING the AG1100+ in a Communicating HVAC System:
EXCLUSIONS
WIRING the AG1100+ in a Communicating HVAC System:
This warranty does not cover damages resulting from use of components or accessories not approved by RectorSeal. 3, and 10 YEAR SECONDARY DRAIN PAN LIMIT-
1.
See equipment manufacturers recommendations for specific wiring instructions.
ED WARRANTY AND LIMITATION OF LIABILITY
1.
See equipment manufacturers recommendations for specific wiring instructions.
This warranty applies only to secondary drain pans installed in the United States and Canada.
RectorSeal warrants to the original consumer purchaser ("Purchaser") of its AquaGuard secondary drain pan products, that they are free from defects in material or work-
manship for a period of three (3) years for Titan pan models, ten (10) years for Goliath and Goliath Furnace models, from the date of purchase. If this product shall prove
to be defective within the three, five or ten (3, or 10) year period from the date
of purchase, it shall be repaired or replaced, at Rectorseal's option, subject to the GENERAL TERMS and CONDITIONS set forth below. This warranty extends only to the
original consumer purchaser and is nontransferable.
EXCLUSIONS
This warranty does not cover damages resulting from the use of corrosive material (including, but not limited to: Acetone, MEK and petroleum-based products); nor dam-
ages resulting from use of components or accessories not approved by RectorSeal.
GENERAL TERMS AND CONDITIONS
To be eligible for the warranty the purchaser must provide RectorSeal with the following:
1. Proof of Purchase (Original Receipt)
2. Installer's Testimony
3. Original Product
4. Original Work Order
5. Photos of Installation
PURCHASER MUST PAY ALL LABOR AND SHIPPING CHARGES NECESSARY TO REPLACE PRODUCT COVERED BY THIS WARRANTY. This warranty shall not
apply to acts of God, nor shall it apply to products which, in the sole judgment of RectorSeal have been subject to negligence, abuse, accident, tampering, misapplication,
alteration; nor due to improper installation, operation or maintenance or storage; nor moved from its original place of installation; nor to other than normal application, use
or service, including but not limited to, operational failures caused by corrosion, rust or other foreign materials in the system. Requests for service under this warranty shall
be made by returning the defective product to the Retail outlet or to RectorSeal as soon as possible after the discovery of any alleged defect. RectorSeal will subsequently
take corrective action as promptly as reasonably possible. No requests for service under this warranty will be accepted if received more than thirty-one (31) days after the
term of the warranty.1hiswarranty sets forth Rectorseal's sole obligation and purchaser's exclusive remedy for defective products. For your benefit and protection register
your product online at www.rectorSeal.com within thirty (30) days of installation. This will initiate the Warranty period and will allow us to contact you, should it become
necessary. In the absence of a recorded product registration, the Warranty period will begin upon product shipment from RectorSeal. In the event that RectorSeal attempts
to contact consumers regarding a recall or other matter, and any damages occur, which could have been avoided by registration by the consumer, RectorSeal shall have
no liability. IN ALL CIRCUMSTANCES, RECTORSEAL'S MAXIMUM LIABILITY SHALL NOT EXCEED THE ACTUAL PURCHASE PRICE PAID FOR THE PRODUCT
ALONE. Warranty claims must be registered with RectorSeal within thirty (30) days of damage or malfunction. RectorSeal reserves the right to visit the site of the instal-
lation or to require documentation of the claim before assuming any responsibility under the provisions of this Warranty. Consumer agrees to inspect the product at the
time of installation for any reasonable discernible defects and, further, agrees to inspect the product annually. Any damages occurring, which could have been avoided by
proper inspection will not be the responsibility of RectorSeal. RECTORSEAL SHALL NOT BE LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT
DAMAGES WHATSOEVER TO THE PURCHASER OR ANY THIRD PARTY. THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL EXPRESSED
WARRANTIES. IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICU-
LAR PURPOSE, SHALL NOT EXTEND BEYOND THE DURATION OF THE APPLICABLE EXPRESSED WARRANTIES PROVIDED HEREIN.
Some states do not allow the exclusion of limitation of incidental and consequential damages or limitations on how long an implied warranty lasts, so the above limitations
or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other legal rights that vary from state to state.
VENUE: Any purchaser or third party actions brought for any reason hereunder shall be commenced in Houston, TX and no other jurisdiction, and such action shall be
governed by and construed in accordance with the laws of the State of Texas. Any notice herein shall be sent by certified or registered mail to 2601 Spenwick Drive,
Houston, TX USA
Installation Instructions
®
AG-1100+ - Magnetic Float Switch
Clean surface with included alcohol pad before mounting with adhesive tape.
Pull pin up to test
Pull pin up to test
Thumb screws
switch
switch
Pull pin up to test
switch
RectorSeal® Houston, TX USA
ATTENTION:
Work Safe, READ THIS!
ATTENTION: FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTI
CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRAN
STOP/READ: This device must be installed in accordance with manufacturer's instruction
electrical codes.
WARNING: Remove electrical shock hazard – DISCONNECT THE POWER BEFORE
Do not use on circuits exceeding 24 volts to avoid damage to switch, shock or fire hazard.
CAUTION: In some situations the switch may cause the unit to rapidly cycle on and off a
Condensation drain must be serviced if thisoccurs.
CAUTION: In any installation where property damage and/or personal injury might result
should be installed.
NOTICE: The AquaGuard AG-1100+ must only be installed by a licensed contractor or
after installation and be kept free from foreign objects, rust or other obstructions that might
INSTALLATION OF FLOAT SWITCH ON DRAIN PAN:
(To ensure proper performance of product, instructions must be followed.)
1.
Disconnect power to unit at main panel.Disconnect power to the low voltage ther
2.
Slide the float switch onto the side of thepan.
3.
Secure switch wires so they will not affect the operation of the float.
4.
Secure the float switch by tightening thumb screws. (fig.1) Do not over tighten.
(fig.1)
WIRING THE AG-1100+ in a Conventional HVAC System:
(To ensure proper performance of product, instructions must be followed.)
Pull pin up to test
1.
Ensure the power is disconnected to the unit at the main panel prior to moving to
switch
Refer to the appliance manufacturer's installation and operating instructions and
2.
Locate the red wire coming from the 24 volt thermostat "R" terminal.
3.
Disconnect or cut red wire. Connect the non-ribbed wire of the switch, using a w
using a wire nut, to the air handler side of the circuit or to terminal in unit. Incor
4.
Test the switch. (At start-up check initial amperage load.)
A. With unit on, test switch by pulling the float pin up. (fig. 2) Unit shoul
B. To test switch responsiveness fill pan with water to ensure that the switc
(fig. 3)
(fig. 3)
(fig. 3)
Standard HVAC Installation w/ optional external alarm or accessory
Standard HVAC Installation w/ optional external alarm or accessory
Standard HVAC Installation w/ optional external alarm or accessory
Standard HVAC Installation w/ optional external alarm or accessory
24 VAC, 5 amps
www.rectorseal.com
US Patent 7,710,283
R50118 0119
Clean surface with included alcoho
AG-1100+
ATTENTION:
Work Safe, READ THIS!
ATTENTION: FAILURE TO READ AND COMPLY W
CAUSE PERSONAL INJURY AND/OR PROPERTY DA
STOP/READ: This device must be installed in accordanc
electrical codes.
WARNING: Remove electrical shock hazard – DISCON
Do not use on circuits exceeding 24 volts to avoid damag
CAUTION: In some situations the switch may cause the
Condensation drain must be serviced if thisoccurs.
CAUTION: In any installation where property damage an
should be installed.
NOTICE: The AquaGuard AG-1200+ must only be inst
after installation and be kept free from foreign objects, rus
INSTALLATION OF FLOAT SWITCH ON
(To ensure proper performance of product, instruction
1.
Disconnect power to unit at main panel. Disconn
2.
Loosen the three thumb screws (fig.1). Unscrew
3.
Slide the float switch onto the side of the pan at t
4.
Finger tighten the top thumb screw first, then the
5.
Secure switch wires so they will not affect the op
(fig.1)
WIRING THE AG-1200+ in a Conventiona
(To ensure proper performance of product, instruction
1.
Ensure the power is disconnected to the unit at
Refer to the appliance manufacturer's installati
2.
Locate the red wire coming from the 24 volt the
3.
Disconnect or cut red wire. Connect the non-ri
using a wire nut, to the air handler side of the c
4.
Test the switch. (At start-up check initial ampe
A. With unit on, test switch by pulling th
B. To test switch responsiveness fill pan w
(fig. 3)
2601 Spenwick Drive, Houston, TX 77055
(P) 800-231-3345 (F) 800-441-0051 www.rectorseal.com
2601 Spenwick Drive, Houston, TX 77055
2601 Spenwick Drive, Houston, TX 77055
(P) 800-231-3345 (F) 800-441-0051 www.rectorseal.com
(P) 800-231-3345 (F) 800-441-0051 www.rectorseal.com
2601 Spenwick Drive, Houston, TX 77055
(P) 800-231-3345 (F) 800-441-0051 www.rectorseal.com
Clean surface
Thumb screws

Publicidad

loading

Resumen de contenidos para RectorSeal AquaGuard AG-1100+

  • Página 1 Requests for service under this warranty shall be made by returning the defective product to the Retail outlet or to RectorSeal as soon as possible after the discovery of any alleged defect. RectorSeal will subsequently take corrective action as promptly as reasonably possible.
  • Página 2 Ver las recomendaciones del fabricante para obtener instrucciones específicas del cableado. de un (I) año partir de la fecha de compra. Si este producto presenta defectos durante el periodo de un año a partir de lafecha de compra, RectorSeal tiene la opcion de EL CABLEADO de AG-1100+ en un sistema de comunicación HVAC:...