Risk Of Electric Shock - Bosch RMH 0002 A Descripción Del Producto / Manual De Instalación

Módulo relé de alta tensión
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 9
English
Functional description
d 2 Circuit form−C relay module with feedback.
Each output is equipped with normally opened (NO) and normally closed (NC) contact.
The outputs are not supervised!
Wiring
Pos.
Marking
1
NC1
2
C1
3
NO1
10
NC2
11
C2
12
NO2
15
FB1 +
16
FB1 −
21
FB2 +
22
FB2 −

RISK OF ELECTRIC SHOCK !

Danger of life with contact of live parts and wires.
" Disconnect power before connecting equipment!
DANGER
Technical Specification
Indication/operation elements
Input voltage (min − max)
Feedback current
Feedback output voltage
Maximum current consumption
− standby mode
− with both relays actuated
Max. relay contact rating
Fuses
Safety standards
EMI / EMC protection
Operating Temperature
Storage Temperature
Permissible relative humidity
Housing material and color
Dimensions (H x W x D)
Weight
Product description RMH 0002 A
Connection
Zone 1 relay
y
Zone 2 relay
y
Feedback zone 1
Feedback zone 1
Feedback zone 2
Feedback zone 2
4 LEDs (2x red, 2x green) / 2 Keys (LED test)
20 V DC − 30 V DC
Maximum 8.5 mA per zone
Maximum 30 V DC
13.5 mA
53.5 mA
10 A at 120 V/230 V AC or 5 A at 30 V DC
F1 = 10 A, F2 = 10 A
IEC 60950 / EN 60950
UL 864 / FCC Part 15
−5 _C . . . 50 _C
−20 _C . . . 60 _C
max. 95%
ABS plastic Cycolac VW300 (UL94 5VA),
semi gloss anthrazit, RAL 7016
approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
approx. 135 g (4.8 ounces)
13 / 32
1
15
(23 _F . . . 122 _F)
(−4 _F . . . 140 _F)
4.998.137.274
2
3
10 11 12
16
21
22
610−4.998.153.981 / A2
ST − FIR / PRM1 / deh

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

4.998.137.274

Tabla de contenido